HOW TO INSTALL THIS SMOKE ALARM

This Smoke Alarm is designed to be mounted on any standard wiring junction box to a 4-inch (10 cm) diagonal size, on ether the ceiling or wall (if allowed by local codes). Read “Recommended Locations For Smoke Alarms” and “Locations to Avoid For Smoke Alarms” before you begin installation.

Tools you will need: Standard Flathead screwdriver.

THE PARTS OF THIS SMOKE ALARM

The Mounting Bracket

Installs onto the junction box.

It has a variety of screw slots to fit most boxes. If a junction box is not already in place, install one. To remove the mounting bracket from the Smoke Alarm base, hold the Smoke Alarm base firmly and twist mounting bracket counterclockwise.

The Power Connector

The Foam Gasket

The foam gasket prevents air currents from coming through the junction box and blowing smoke away from the sensor. It must be installed to comply with UL standards. When installing the foam gasket, line up the cut-outs with the power input block on the Smoke Alarm.

Parts of the Smoke Alarm

1 Mounting slot and screw (1 of 2)

2 Junction box

3 Mounting bracket

4 Mounting Bracket Alignment Arrow

5 Mounting slot and screw (1 of 2)

6 Wire strip gauge

7 Neutral (white) AC wire

8 Hot (black) AC wire

9 Interconnect wire

10 Foam gasket

11 Alignment Tab On Alarm

12 Turn to attach to bracket

The power connector plugs into a power input block on the Smoke Alarm and supplies it AC power.

•Black wire is “hot.” •White wire is neutral.

•Orange wire is used for interconnect.

If you need to remove the power connector, turn POWER OFF first. To remove the power connector, insert a flat screwdriver blade between the power connector and the security tab inside the power input block. Gently pry back the tab and pull the connector free.

13 Turn to remove from bracket

Make sure the Alarm is not receiving excessively noisy power. Examples of noisy power could be major appliances on the same circuit, power from a generator or solar power, light dimmer on the same circuit or mounted near fluorescent lighting. Excessively noisy power may cause damage to your Alarm.

FOLLOW THESE INSTALLATION STEPS

The basic installation of this Smoke Alarm is the similar whether you want to install one Smoke Alarm, or interconnect more than one Smoke Alarm. If you are interconnecting more than one Smoke Alarm, you MUST read “Special Requirements For Interconnected Smoke Alarms” below before you begin installation.

ELECTRICAL SHOCK HAZARD! Turn off power before starting installation!

1.Remove the mounting bracket from the base. Install the mounting bracket to the junction box

2.Set the foam gasket against the back of the Smoke Alarm.

3.Using wire nuts, connect the power connector to the household wiring.

STAND-ALONE ALARM ONLY:

Connect the white wire on the power connector to the neutral wire in the junction box.

Connect the black wire on the power connector to the hot wire in the junction box.

Tuck the orange wire inside the junction box. It is used for interconnect only.

INTERCONNECTED UNITS ONLY:

Strip off about 1/2” (12 mm) of the plastic coating on the orange wire on the power connector.

Connect the white wire on the power connector to the neutral wire in the junction box.

Connect the black wire on the power connector to the hot wire in the junction box.

Connect the orange wire on the power connector to the inter- connect wire in the junction box. Repeat for each unit you are interconnecting. Never connect the hot or neutral wires in the junction box to the orange interconnect wire.

4.Plug the power connector into the back of the Smoke Alarm.

5.Line up the alignment tab on the base with the alignment tab on the mounting bracket. Turn the Smoke Alarm clockwise (right) until you hear the unit snap into place.

6.Check all connections.

Improper wiring of the power connector or the wiring leading to the power connector will cause damage to the Alarm and may lead to a non-functioning Alarm.

STAND-ALONE ALARM ONLY:

If you are only installing one Smoke Alarm, restore power to the junction box.

INTERCONNECTED UNITS ONLY:

If you are interconnecting multiple Smoke Alarms, repeat steps 1-6 for each Smoke Alarm in the series. When you are finished, restore power to the junction box.

ELECTRICAL SHOCK HAZARD! Do not restore power until all smoke alarms are completely installed. Restoring power before installation is complete may result in serious electrical shock, injury or death.

7.Make sure the Smoke Alarm is receiving AC power. Under normal operation, the green power indicator light will shine continuously. If the power indicator light does not light, TURN OFF POWER TO THE JUNCTION BOX and recheck all connections. If all connec- tions are correct and the power indicator still does not light when you restore the power, the unit should be replaced immediately.

8.Test the Smoke Alarm. Press and hold the test button on the cover of the unit until the alarm sounds (the unit may continue to alarm for a few seconds after you release the button). During testing, you will hear a loud, repeating horn pattern: 3 beeps, pause, 3 beeps, pause. In an interconnected series, you must test each Smoke Alarm individually.

If any Smoke Alarm does not alarm, TURN OFF POWER and recheck connections. If any Smoke Alarm still does not alarm when you test it after restoring power, replace it immediately.

2

Page 2
Image 2
BRK electronic SA100B HOW to Install this Smoke Alarm, Parts of this Smoke Alarm, Follow These Installation Steps

SA100B specifications

The BRK electronic SA100B is a highly regarded smoke detector, designed to provide reliable and efficient fire safety for homes and commercial spaces. This smoke detector is particularly notable for its advanced features and innovative technologies, making it a top choice for safeguarding lives and property from the imminent threat of fire.

One of the standout features of the SA100B is its photoelectric sensing technology. This type of sensor is adept at detecting smoldering fires that produce dense smoke, which often occurs in household materials like upholstery and mattresses. Unlike traditional ionization detectors that may trigger false alarms from cooking smoke, the photoelectric sensor in the SA100B intelligently differentiates between smoke types, reducing unnecessary disturbances while maintaining high sensitivity.

The SA100B is also equipped with a built-in 10-year battery, providing peace of mind without the hassle of frequent battery changes. This lithium battery is designed to last the lifetime of the detector, ensuring uninterrupted operation and lower maintenance for users. The device features a convenient low-battery indicator, alerting homeowners when it's time to replace the unit itself at the end of its service life.

Installation of the BRK electronic SA100B is straightforward due to its compact and lightweight design. The unit can be mounted on walls or ceilings, giving users flexibility in optimal placement for smoke detection coverage. With a sleek, modern appearance, it is also designed to blend seamlessly into any decor.

Safety is further enhanced by the device’s loud 85-decibel alarm, ensuring occupants are alerted promptly in the event of smoke detection. The SA100B also features a test/silence button, allowing users to routinely check the detector’s functionality and silence alarms caused by non-threatening conditions such as cooking smoke.

Overall, the BRK electronic SA100B smoke detector combines advanced sensing technologies with user-friendly features, making it an essential component of any fire safety plan. Its robust design, longevity, and efficiency serve to protect families and businesses alike, reinforcing the importance of smoke detection in fire prevention. Investing in the SA100B not only fulfills legislative mandates for fire safety but also promotes peace of mind, ensuring that occupants can feel safe and secure in their environment.