HUMIDITY SENSING |
| MODEL QTXE110SFLT |
www.broan.com | Page | |
| To register this product visit: |
FAN / FLUORESCENT LIGHT / NIGHT LIGHT
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OB- SERVE THE FOLLOWING:
1.Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
2.Before servicing or cleaning unit, switch power off at service panel and lock the ser- vice disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3.Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including
4.Sufficientairisneededforpropercombustion and exhausting of gases through the flue (chimney) of fuel burning equipment to pre- vent backdrafting. Follow the heating equip- ment manufacturer’s guideline and safety standards such as those published by the
National Fire Protection Association (NFPA), and the American Society for Heating, Re- frigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
5.When cutting or drilling into wall or ceiling, do notdamageelectricalwiringandotherhidden utilities.
6.Ducted fans must always be vented to the outdoors.
7.Acceptableforuseoveratuborshowerwhen connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.
8.This unit must be grounded.
CAUTION
1.For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2.This product is designed for installation in flat ceilings only. DO NOT MOUNT THIS PRODUCT IN A WALL.
3.To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4.Please read specification label on product for further information and requirements.
Installer: Leave this manual
with the homeowner.
OPERATION
The humidity control and fan can be
SENSOR OPERATION
This humidity-sensing fan responds to:
(a)rapid to moderate humidity increases and (b) humidity above a
STATUS INDICATOR
This indicator can only be seen by looking directly at it. Normal mode is
MANUAL ON WITH TIMED OFF
For odor or vapor control, the fan can be en- ergized by cycling its
To manually energize the fan:
1.Go to Step 2 if switch is already on; otherwise, turn switch on for more than 1 second.
2.Switch off for less than 1 second.
3.Switch back on and fan will turn on.
SENSITIVITY ADJUSTMENT
“SENSITIVITY” has been factory set for most shower applications. If the fan is in a tub area or is used for dampness control, the “SENSITIVITY” may need to be in- creased toward maximum (“MAX.”). If the control is responding too often to changing environmental conditions, adjustment to- ward less (“MIN.”) “SENSITIVITY” may be required. To adjust the “SENSITIVITY”:
1.Turn power off at electrical service panel.
2.Through the grille, locate the “SENSITIVITY” screwdriver slot.
3.Using a small,
4.Turn power on and check operation by turning on shower or other humidity source until fan turns on.
5.Repeat above steps if necessary.
TIMER ADJUSTMENT
This
To adjust the “TIMER”:
1.Disconnect power at electrical service panel.
2.Through the grille, locate the “TIMER” screwdriver slot.
3.Using a small,
4.Check operation by cycling power switch as instructed under “MANUAL ON WITH TIMED OFF” or by turning on a humidity source until fan turns on.
5.Check “TIMER” setting with watch or clock after turning humidity source off if it was turned on it Step 4.
6.Repeat above steps if necessary.
CLEANING & MAINTENANCE
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dusting brush attachment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the motor with the exact service motor. The impeller should also be replaced.
SENSOR CLEANING
The humidity sensor is mounted in the grille. The sensor will operate most reliably when cleaned occasionally as follows:
1.Disconnect power at service entrance.
2.Remove the grille. Use a dry dustcloth, clean toothbrush, or lightly vacuum to clean sensor and grille. DO NOT USE ABRASIVE CLOTH, STEEL WOOL PADS, OR SCOURING POWDERS.
3.DO NOT USE cleaning sprays, solvents, or water on or near the sensor!