![Bryan “Flexible Water Tube”](/images/new-backgrounds/52488/524881x1.webp)
Form No. 6700 (Rev. 5/07)
Bryan “Flexible Water Tube”
HE-CLM Series Water Boilers
900,000 to 3,000,000 BTUH
Forced draft gas fired
Guaranteed 85% efficiency
A. Heavy steel boiler frame, built and stamped in accordance with the ASME Boiler Code, Section IV.
B. Large volume water leg downcomers promote rapid internal circulation, temperature equalization and efficient heat transfer.
C. Bryanbentwatertubesareflexible,individuallyreplaceablewith- out welding or rolling. Never more than two tube configurations.
D. Boiler tube and furnace area access panel: heavy gauge steel casing with 2" high temperature ceramic fiber and insulation, bolted and tightly sealed to boiler frame.
E. Jacket access panels make the interior of the boiler easily accessible for service and inspection.
F. Steel boiler jacket with 16 gauge
| G. Minimum sized flue vent. |
| H. Forced draft, flame retention head type burner. Efficient |
| combustion and quiet operation. |
| I. All controls, gauges, relief valve(s) are factory installed and |
| wired and easily accessible for servicing. |
| J. Electrical box: all controls installed and connected to terminal |
| strip. |
Model | K . Water side interior accessible for cleanout and inspection, |
front and rear openings, upper and lower drums. | |
| L. Steel plate boiler base with lightweight, high temperature |
| insulating firebrick combustion chamber, designed for maximum |
| combustion efficiency. |
•With
•What's more,
BOILER | INPUT | OUTPUT @ 85% EFFICIENCY(1) | HTG.SURFACE | APPROX. SHIP | |
MODEL | MBH (KW) | MBH (KW) | HP (KW) | SQ.FT.(M2) | LBS. (KG) |
900 (264) | 765 (224) | 23 (224) | 171 (15.9) | 2,110 (957) | |
1,200 (352) | 1,020 (299) | 30 (299) | 227 (21.1) | 2,400 (1,089) | |
1,500 (440) | 1,275 (374) | 38 (374) | 282 (26.2) | 2,860 (1,297) | |
1,800 (527) | 1,530 (448) | 46 (448) | 338 (31.4) | 3,200 (1,452) | |
2,100 (615) | 1,785 (523) | 53 (523) | 394 (36.6) | 3,740 (1,697) | |
2,400 (703) | 2,040 (598) | 61 (598) | 451 (41.9) | 4,200 (1,905) | |
2,700 (791) | 2,295 (672) | 69 (672) | 506 (47.0) | 4,740 (2,150) | |
3,000 (879) | 2,550 (747) | 76 (747) | 564 (52.4) | 5,175 (2,348) |
NOTES : (1) Output and horsepower based on an average natural gas combustion efficiency of 85%.