CONDENSER ONLY RATINGS* Continued

CONDENSER ONLY RATINGS* Continued

SST

 

 

 

CONDENSER ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

 

 

 

°F

 

55

65

75

85

95

105

115

125

 

 

 

 

 

 

 

 

 

 

550A042-F

 

TCG

41.4

39.2

37.0

34.8

32.5

30.2

27.8

25.3

30

SDT

72.3

82.0

91.8

102.0

111.0

121.0

130.0

140.0

 

KW

1.85

2.10

2.39

2.72

3.07

3.46

3.89

4.36

 

 

 

 

 

 

 

 

 

 

 

TCG

45.4

43.0

40.6

38.2

35.7

33.2

30.6

27.8

35

SDT

73.7

83.4

93.1

103.0

112.0

122.0

131.0

141.0

 

KW

1.86

2.12

2.41

2.74

3.09

3.49

3.92

4.39

 

 

 

 

 

 

 

 

 

 

 

TCG

49.6

47.0

44.5

41.8

39.1

36.4

33.5

30.5

40

SDT

75.2

84.8

94.4

104.0

114.0

123.0

133.0

142.0

 

KW

1.88

2.14

2.43

2.76

3.12

3.51

3.94

4.41

 

 

 

 

 

 

 

 

 

 

 

TCG

54.0

51.3

48.5

45.7

42.7

39.8

36.7

33.3

45

SDT

76.7

86.3

95.9

106.0

115.0

125.0

134.0

143.0

 

KW

1.89

2.16

2.45

2.78

3.14

3.54

3.97

4.44

 

 

 

 

 

 

 

 

 

 

 

TCG

58.8

55.8

52.8

49.7

46.6

43.3

39.9

36.3

50

SDT

78.4

87.9

97.4

107.0

117.0

126.0

135.0

144.0

 

KW

1.92

2.18

2.47

2.80

3.17

3.57

4.00

4.47

 

 

 

 

 

 

 

 

 

 

 

TCG

63.8

60.6

57.4

54.0

50.6

47.1

43.4

39.5

55

SDT

80.2

89.6

99.1

109.0

118.0

127.0

137.0

145.0

 

KW

1.94

2.20

2.50

2.83

3.20

3.60

4.03

4.50

 

 

 

 

 

 

 

 

 

 

550A048-F

 

TCG

45.8

43.3

40.9

38.5

36.0

33.6

31.0

28.4

30

SDT

72.0

82.0

92.0

102.0

112.0

122.0

132.0

142.0

 

KW

2.11

2.40

2.73

3.09

3.52

3.98

4.51

5.09

 

 

 

 

 

 

 

 

 

 

 

TCG

50.6

47.9

45.2

42.6

39.9

37.2

34.4

31.5

35

SDT

72.0

82.0

92.0

102.0

112.0

122.0

132.0

142.0

 

KW

2.10

2.39

2.71

3.08

3.49

3.96

4.48

5.06

 

 

 

 

 

 

 

 

 

 

 

TCG

55.7

52.8

49.9

47.0

44.1

41.1

38.1

34.9

40

SDT

72.3

82.1

92.0

102.0

112.0

122.0

132.0

142.0

 

KW

2.10

2.38

2.70

3.06

3.47

3.93

4.45

5.02

 

 

 

 

 

 

 

 

 

 

 

TCG

60.9

57.8

54.7

51.7

48.6

45.4

42.1

38.5

45

SDT

73.6

83.2

92.7

102.0

112.0

122.0

132.0

142.0

 

KW

2.13

2.40

2.71

3.06

3.46

3.91

4.42

4.99

 

 

 

 

 

 

 

 

 

 

 

TCG

66.3

63.0

59.7

56.4

53.1

49.8

46.2

42.5

50

SDT

75.1

84.6

94.1

104.0

113.0

123.0

132.0

142.0

 

KW

2.17

2.44

2.75

3.09

3.48

3.92

4.41

4.96

 

 

 

 

 

 

 

 

 

 

 

TCG

72.1

68.5

65.0

61.4

57.8

54.2

50.5

46.5

55

SDT

76.7

86.1

95.6

105.0

114.0

124.0

133.0

143.0

 

KW

2.21

2.48

2.79

3.14

3.52

3.95

4.43

4.96

 

 

 

 

 

 

 

 

 

 

550A060-H

 

TCG

57.7

54.6

51.6

48.5

45.4

42.1

38.6

34.6

30

SDT

75.9

85.1

94.3

103.4

112.5

121.6

130.6

139.4

 

KW

8.82

9.97

11.22

12.59

14.12

15.83

17.63

19.46

 

TCG

63.5

60.1

56.8

53.3

49.9

46.3

42.4

38.1

35

SDT

77.7

86.8

95.9

104.9

114.0

122.9

131.8

140.5

 

KW

8.98

10.12

11.38

12.76

14.28

15.98

17.79

19.72

 

TCG

69.6

65.9

62.2

58.4

54.6

50.6

46.3

41.6

40

SDT

79.6

88.5

97.5

106.5

115.4

124.3

133.0

141.6

 

KW

9.16

10.29

11.56

12.94

14.44

16.15

17.95

19.9

 

TCG

76.1

72.0

67.9

63.8

59.5

55.0

50.3

45.10

45

SDT

81.6

90.5

99.4

108.2

117.0

125.7

134.3

142.7

 

KW

9.36

10.48

11.76

13.13

14.63

16.32

18.11

20.05

 

TCG

82.8

78.4

73.9

69.3

64.5

59.6

54.3

48.6

50

SDT

83.7

92.5

101.2

110.0

118.6

127.2

135.6

143.8

 

KW

9.57

10.68

11.97

13.36

14.84

16.5

18.28

20.19

55

TCG

89.8

85.0

80.0

75.0

69.7

64.3

58.5

52.3

SDT

85.9

94.5

103.2

111.8

120.3

128.7

136.9

144.9

 

KW

9.80

10.9

12.19

13.58

15.07

16.71

18.45

20.34

*ARI listing applies only to systems shown in Combination Ratings table. KW — Outdoor Unit Kilowatts Only

SDT — Saturated Temperature Leaving Compressor (°F) SST — Saturated Temperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh).

—40—

Page 40
Image 40
Bryant warranty CONDENSER ONLY RATINGS* Continued, 550A042-F, 550A048-F, 550A060-H, 40