Bryant 550A warranty SPECIFICATIONS Continued

Models: 550A

1 44
Download 44 pages 56.75 Kb
Page 5
Image 5

SPECIFICATIONS Continued

UNIT SIZE-SERIES

042-F

 

048-F

 

060-H

Operating Weight (Lb)

247

 

295

 

331

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

 

Unit Volts—Hertz—Phase

 

 

208/230—60—1

 

 

 

 

 

 

 

 

Operating Voltage Range*

 

 

187—253

 

 

 

 

 

 

 

 

 

Compressor— Rated Load Amps

18.6

 

20.5

 

27.6

 

 

 

 

 

 

 

 

 

 

Locked Rotor Amps

105.0

 

109.0

 

158.0

 

 

 

 

 

 

 

 

Condenser Fan Motor—Full Load Amps

1.1

 

1.4

 

1.4

 

 

 

 

 

 

 

 

Min Unit Ampacity for Wire Sizing

24.4

 

27.0

 

35.9

 

 

 

 

 

 

 

 

Min Wire Size (60°C Copper) AWG†

10

 

10

 

8

 

 

 

 

 

 

 

 

Min Wire Size (75°C Copper) AWG†

10

 

10

 

8

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (60°C Copper)‡

80

 

73

 

85

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (75°C Copper)‡

76

 

70

 

80

 

 

 

 

 

 

 

 

Max Branch Circuit Fuse or

 

 

 

 

 

Circuit Breaker Size (Amps)

40

 

40

 

60

 

 

 

 

 

 

 

 

COMPRESSOR & REFRIGERANT

 

 

 

 

 

Compressor— Type

 

 

Scroll

 

 

 

 

 

 

 

 

Temperature & Current Protection

 

 

Internal Line Break

 

 

 

 

 

 

 

 

Refrigerant— Type

 

 

Puron® (R-410A)

 

 

 

 

 

 

 

 

 

Amount (Lb)

8.75

 

10.13

 

11.50

 

 

 

 

 

 

 

 

CONDENSER COIL & FAN

 

 

 

 

 

Coil Face Area (Sq Ft)

18.2

 

18.2

 

18.2

 

 

 

 

 

 

 

 

Fins per In.—Rows—Circuits

25—1—3

 

20—2—5

 

20—2—5

 

 

 

 

 

 

 

 

Fan Motor—HP (PSC) & RPM

1/5 & 825

 

1/4 & 1125

 

1/4 & 1125

 

 

 

 

 

 

 

 

Volts—Hertz—Phase

 

 

208/230—60—1

 

 

 

 

 

 

 

 

 

Condenser Airflow (CFM)

2800

 

3400

 

3400

 

 

 

 

 

 

 

 

OPTIONAL EQUIPMENT

 

 

 

 

 

Support Feet

 

 

KSASF0101AAA

 

 

 

 

 

 

 

 

Coastal Filter

 

 

KAACF0801MED

 

Time Delay Relay

 

 

KAATD0101TDR

 

 

 

 

 

 

 

 

Cycle Protector

 

 

KSACY0101AAA

 

 

 

 

 

 

 

 

Crankcase Heater

 

 

KAACH1201AAA

 

 

 

 

 

 

 

 

Start Assist—Capacitor/Relay Type

KSAHS1501AAA

 

 

KSAHS1601AAA

 

 

 

 

 

 

 

 

Start Assist—PTC Type

 

 

KAACS0201PTC

 

 

 

 

 

 

 

 

TXV (Hard Shutoff)

KSATX0301PUR

 

KSATX0401PUR

 

KSATX0501PUR

 

 

 

 

 

 

 

 

Piston Body

 

 

KSAPX0101PIS

 

 

 

 

 

 

 

 

Filter Drier (Suction Line)

 

 

KH45LG141 (RCD)

 

 

 

 

 

 

 

 

Evaporator Freeze Thermostat**

 

 

KAAFT0101AAA

 

 

 

 

 

 

 

 

Liquid-Line Solenoid Valve

 

 

KAALS0201LLS

 

 

 

 

 

 

 

 

Winter Start Control**

 

 

KAAWS0101AAA

 

 

 

 

 

 

 

 

Low-Ambient Pressure Switch

 

 

KSALA0301410

 

 

 

 

 

 

 

 

MotorMaster® Low-Ambient Controller ††

 

 

KSALA0401AAA

 

 

 

 

 

 

 

 

Ball Bearing Fan Motor

HC38GE231 (RCD)

 

HC40GE232 (RCD)

 

 

 

 

 

 

 

 

 

Thermidistat™ Control—

 

 

 

 

 

Programmable Thermostat with Humidity Control

 

 

TSTATBBPRH01-B

 

 

 

 

 

 

 

 

 

Thermostat—Auto Changeover, 7-Day Programmable,

 

 

 

 

 

°F/°C, 1-Stage Heat, 1-Stage Cool

 

 

TSTATBBPAC01-B

 

 

 

 

 

 

 

 

 

Thermostat—Auto Changeover, Non-Programmable,

 

 

 

 

 

°F/°C, 1-Stage Heat, 1-Stage Cool

 

 

TSTATBBNAC01-C

 

 

 

 

 

 

 

 

 

Thermostat—Manual Changeover, 5-2 Day Programmable,

 

 

 

 

 

°F/°C, 1-Stage Heat, 1-Stage Cool

 

 

TSTATBBSAC01

 

 

 

 

 

 

 

 

 

Builder’s Thermostat—Manual Changeover,

 

 

 

 

 

Non-Programmable, °F/°C, 1-Stage Heat, 1-Stage Cool

 

 

TSTATBBBAC01-B

 

 

 

 

 

 

 

 

Outdoor Air Temperature Sensor

 

 

TSTATXXSEN01-B

 

 

 

 

 

 

 

 

Backplate for Non-Programmable Thermostat

 

 

TSTATXXNBP01

 

 

 

 

 

 

 

 

Backplate for Programmable Thermostat

 

 

TSTATXXPBP01

 

 

 

 

 

 

 

 

Backplate for Builder’s Thermostat

 

 

TSTATXXBBP01

 

 

 

 

 

 

 

 

Backplate for Standard Thermostat

 

 

TSTATXXSBP01

 

 

 

 

 

 

 

 

Thermostat Conversion Kit (4 to 5 wire)—10 Pack

 

 

TSTATXXCNV10

 

 

 

 

 

 

 

 

Evolution Controls

 

 

See chart.

 

*Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

**See low-ambient controller Installation Instructions for application.

††Fan motor with ball bearings required.

N/A — Not Applicable.

NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

—5—

Page 5
Image 5
Bryant 550A warranty SPECIFICATIONS Continued