Bryant 581J specifications Physical Data Cooling, Tons

Models: 581J

1 66
Download 66 pages 2.92 Kb
Page 14
Image 14

TABLE 10 – PHYSICAL DATA

(COOLING)

7.5 - 8.5 TONS

Refrigeration System

Evap. Coil

#Circuits / # Comp. / Type R--- 410a charge A/B (lbs --- oz)

Metering device High--- press. Trip / Reset (psig) Low--- press. Trip / Reset (psig)

Compressor Capacity Staging (%)

 

581J*08D

 

581J*09D

 

 

 

 

 

 

 

 

 

2 / 2

/ Scroll

 

2 / 2

/ Scroll

 

 

 

9 --- 10

/ 9 --- 10

 

9 --- 19

/ 9 --- 14

 

TXV

 

TXV

 

630

/ 505

 

630

/ 505

 

54

/ 117

 

54

/ 117

 

50%

/ 100%

 

50%

/ 100%

 

 

 

 

 

 

Evap. fan and motor

Material (Tube/Fin)

 

Cu / Al

 

Cu / Al

 

 

Coil type

 

3/8” RTPF

 

3/8” RTPF

Rows / FPI

 

4 / 15

 

4 / 15

total face area (ft2)

 

11.1

 

11.1

Condensate drain conn. size

 

3/4”

 

3/4”

 

 

 

 

 

581J

Standard Static

3 phase

 

 

 

 

Medium Static

3 phase

 

 

 

 

High Static

3 phase

 

 

Cond. Coil

Motor Qty / Drive type Max BHP RPM range

motor frame size Fan Qty / Type Fan Diameter (in)

Motor Qty / Drive type Max BHP RPM range

motor frame size Fan Qty / Type Fan Diameter (in)

Motor Qty / Drive type Max BHP RPM range

motor frame size Fan Qty / Type Fan Diameter (in)

1 / Belt

1.7

518--- 733

56

1 / Centrifugal

15 x 15

1 / Belt

2.4

690--- 936

56

1 / Centrifugal

15 x 15

1 / Belt

3.7

838--- 1084

56

1 / Centrifugal

15 x 15

1 / Belt

1.7

518--- 733

56

1 / Centrifugal

15 x 15

1 / Belt

2.4

690--- 936

56

1 / Centrifugal

15 x 15

1 / Belt

3.7

838--- 1084

56

1 / Centrifugal

15 x 15

Cond. fan / motor

Filters

Material (Tube/Fin)

 

 

Cu / Al

 

 

Cu / Al

 

 

 

 

Coil type

 

 

3/8” RTPF

 

 

3/8” RTPF

Rows / FPI

 

 

2 / 17

 

 

2 / 17

Total Face Area (ft2)

 

 

25.1

 

 

25.1

Qty / Motor drive type

 

 

2 / direct

 

 

2 / direct

 

 

 

 

Motor HP / RPM

 

 

1/4 / 1100

 

 

1/4 / 1100

Fan diameter (in)

 

 

22

 

 

22

RA Filter # / size (in)

 

4

/ 20 x 20 x 2

 

4

/ 20 x 20 x 2

 

 

OA inlet screen # / size (in)

 

1

/ 20 x 24 x 1

 

1

/ 20 x 24 x 1

 

 

 

 

 

 

 

14

Page 14
Image 14
Bryant 581J specifications Physical Data Cooling, Tons