CURBS & WEIGHTS DIMENSIONS - 581J04-06 (cont.)
581J
C10379
Fig. 2 - Dimensions 581J04-06
C
B
D
A
C08337
Fig. 3 - Service Clearance
|
|
| |
LOC | DIMENSION | CONDITION | |
| 48” (1219 mm) | Unit disconnect is mounted on panel | |
A | 18” (457 mm) | No disconnect, convenience outlet option | |
18” (457 mm) | Recommended service clearance | ||
| |||
| 12” (305 mm) | Minimum clearance | |
|
|
| |
| 42” (1067 mm) | Surface behind servicer is grounded (e.g., metal, masonry wall) | |
B | 36” (914 mm) | Surface behind servicer is electrically | |
| Special | Check for sources of flue products within | |
|
|
| |
C | 36” (914 mm) | Side condensate drain is used | |
18” (457 mm) | Minimum clearance | ||
| |||
|
|
| |
| 48” (1219 mm) | No flue discharge accessory installed, surface is combustible material | |
D | 42” (1067 mm) | Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) | |
36” (914 mm) | Surface behind servicer is electrically | ||
| |||
| Special | Check for adjacent units or building fresh air intakes within | |
|
|
|
17