Bryant 591B instruction manual Accessoryusage, B. Install Liquid-Linefilter Drier

Models: 591B

1 12
Download 12 pages 33.43 Kb
Page 4
Image 4
TABLE 2—ACCESSORY USAGE

TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

UNIT SIZE

LIQUID

 

VAPOR

 

VAPOR (LONG LINE)

Connection Diameter

 

Tube Diameter

Connection Diameter

 

Tube Diameter

Connection Diameter

Tube Diameter

 

 

 

018, 024

3/8

 

3/8

5/8

 

5/8

5/8

3/4

030, 036

3/8

 

3/8

3/4

 

3/4

3/4

7/8

042, 048

3/8

 

3/8

7/8

 

7/8

7/8

1-1/8

060

3/8

 

3/8

7/8

 

1-1/8

7/8

1-1/8

 

 

 

 

 

 

 

 

 

NOTES:

1.Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual—Air Conditio ners and Heat Pumps Using Puron®.

2.Do not apply capillary tube indoor coils to these units.

TABLE 2—ACCESSORY USAGE

 

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

ACCESSORY

LOW-AMBIENT

LONG-LINE

SEA COAST

APPLICATIONS

APPLICATIONS*

APPLICATIONS

 

 

(BELOW 55°F)

(OVER 50 FT)

(WITHIN 2 MILES)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Yes

Yes

No

Capacitor and Relay

 

 

 

MotorMaster® Control,

 

 

 

or

Yes

No

No

Low-Ambient Pressure Switch

 

 

 

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

 

 

 

or

No

See Long-Line Application Guideline

No

Hard Shutoff TXV

 

 

 

Ball Bearing Fan Motor

Yes‡

No

No

*For Tubing Sets between 50 and 175 ft horizontal or 20 ft vertical differential, refer to the Application Guideline and Service Manual—Air Condition ers and Heat Pumps Using Puron®.

† Only when low-pressure switch is used.

‡ Required for low-ambient controller (full modulation feature) and MotorMaster® Control only.

CAUTION: To prevent improper performance and/or unit component failures, do not leave system open to atmosphere any longer than minimum required for instal- lation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.

CAUTION: To prevent improper performance or equip- ment failure this caution must be followed. If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. Do not bury lines over 36 in. in length.

CAUTION: To prevent damage to unit or service valves observe the following:

• Use a brazing shield.

Wrap service valves with wet cloth or use a heat sink material.

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft, substan- tial capacity and performance losses can occur. Following the recommendations in the Application Guideline and Service

—4—

Manual—Air Conditioners and Heat Pumps Using Puron® Refrig- erant will reduce these losses. Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.

There are no buried-line applications greater than 36 in.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

A. OUTDOOR UNIT CONNECTED TO FACTORY- APPROVED INDOOR UNIT

Factory refrigerant charge is for a 15 ft line set. Outdoor unit contains correct system refrigerant charge for operation with ARI rated indoor unit. Check refrigerant charge for maximum effi- ciency. The charge must be adjusted based on the actual line set length. Add or subtract 0.6 oz/ft for line sets longer or shorter than 15 ft.

B. INSTALL LIQUID-LINE FILTER DRIER

CAUTION: To avoid performance loss and compressor failure, installation of filter drier in liquid line is required.

Refer to Fig. 6 and install filter drier as follows:

1.Braze 5-in. connector tube to liquid service valve. Wrap filter drier with damp cloth.

2.Braze filter drier between connector tube and liquid tube to indoor coil. Flow arrow must point towards indoor coil.

Page 4
Image 4
Bryant 591B instruction manual Accessoryusage, B. Install Liquid-Linefilter Drier