Table 3 – Required Subcooling
664B
A08406
Step 4 — Indoor Airflow and Airflow Adjust- ments
NOTE: For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity.
Table 4 shows dry coil air delivery for horizontal discharge units. Tables
NOTE: Be sure that all supply- and
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power to the unit and install lockout tag before changing blower speed.
Airflow can be changed by changing the lead connections at the blower motor. To change motor speeds, reposition wire at fan motor speed terminals labeled
Remove the speed tap connector labeled 1 through 5 on the motor. While looking at the connector end that is inserted into the motor, gently pry the locking tab outward and remove the wire from the connector. Insert the wire into the desired tap until it locks into place. Be sure new airflow meets the range noted above and minimum electric heat CFM, if equipped. Refer to Table 2 and 4.
All model sizes are factory wired or rated airflow operation.
A08412
Fig. 12 - Motor Speed Selection
FOR 208/230V BLOWER MOTORS
The motor lead speed connections are as follows:
SIZE | RATED AIRFLOW | HIGH AIRFLOW |
024 | Tap 1 | Tap 3 |
030 | Tap 2 | Tap 4 |
036 | Tap 1 | Tap 3 |
042 | Tap 2 | Tap 4 |
| RATED AIRFLOW | HIGH AIRFLOW | ||
SIZE | Low | High | Low | High |
| Stage | Stage | Stage | Stage |
|
|
|
|
|
048 | Tap 1 | Tap 3 | Tap 2 | Tap 4 |
060 | Tap 1 | Tap 3 | Tap 2 | Tap 4 |
9