SPECIFICATIONS
| UNIT |
|
|
|
|
| |
| OPERATING WEIGHT (Lb) | 188 | 243 | 282 | 327 |
| |
| ELECTRICAL |
|
|
|
|
| |
| Unit |
| |||||
| Operating Voltage Range* |
| |||||
| Compressor— Rated Load Amps | 10.6 | 14.1 | 22.3 | 28.3 |
| |
|
| Locked Rotor Amps | 64.0 | 66.0 | 96.0 | 130.0 |
|
| Condenser Fan | 0.5 | 0.84 | 1.1 | 1.1 |
| |
| Min Unit Ampacity for Wire Sizing | 13.8 | 18.5 | 29.0 | 36.5 |
| |
| Min Wire Size (60°C Copper) AWG† | 14 | 14 | 10 | 8 |
| |
| Min Wire Size (70°C Copper) AWG† | 14 | 14 | 10 | 8 |
| |
| Max Wire Length (60°C) (Ft)‡ | 57 | 43 | 69 | 91 |
| |
| Max Wire Length (70°C) (Ft)‡ | 55 | 41 | 66 | 56 |
| |
| Max Branch Circuit Fuse Size** | 20 | 30 | 45 | 60 |
|
| COMPRESSOR AND REFRIGERANT |
|
|
|
|
|
|
| |
| Compressor— | Manufacturer |
|
| Bristol |
|
|
| |
|
| Type |
|
| Reciprocating |
|
|
| |
|
|
|
|
|
|
|
| ||
| Temperature and Current Protection |
| Internal Overload |
|
|
| |||
| Refrigerant— | Type |
| Puron® |
|
|
| ||
|
| Amount (Lb) | 6.1 |
|
| 13.9 |
| 15.3 |
|
|
| 10.0 |
|
|
| ||||
| Metering Device |
|
| Puron TXV Balance Port Hard Shutoff |
|
|
| ||
| CONDENSER COIL AND FAN |
|
|
|
|
|
|
|
|
|
| 10.8 | 12.12 |
| 18.2 |
| 18.2 |
| |
| Fins per |
|
|
|
| ||||
| Fan | 1/15 and 825 | 1/8 and 825 |
| 1/5 and 825 |
| 1/5 and 825 |
| |
|
|
|
|
|
|
| |||
| Condenser Airflow (CFM) |
| 1500 | 2500 |
| 3000 |
| 3100 |
|
| OPTIONAL EQUIPMENT |
|
|
|
|
|
|
|
|
| Support Feet |
|
| KSASF0101AAA |
|
|
| ||
| Coastal Filter |
|
| KAACF0801MED |
|
|
| ||
| Snow Stand |
| KHASS0106MPK |
|
| KHASS0206MPK |
|
|
|
| Thermostat, Auto Changeover, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| |||||
|
|
|
|
|
| ||||
| Thermostat, Auto Changeover, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |
| Thermidistat Control, Programmable/Non- |
|
|
|
| ||||
| Programmable Thermostat with Humidity Control |
|
|
|
| ||||
| Outdoor Air Temperature Sensor |
|
|
|
|
| |||
| Backplate for |
| TSTATXXNBP01 |
|
|
| |||
| Backplate for Programmable Thermostat |
| TSTATXXPBP01 |
|
|
| |||
| Thermostat Conversion Kit (4 to 5 |
| TSTATXXCNV10 |
|
|
|
* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
†If wire is applied at ambient greater than 30°C (86°F), consult Table
‡Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%. **
NOTES: 1. Copper wire must be used from service disconnect to unit.
2.All motors and compressors contain internal overload protection.
3.This product may not be used in