HEAT PUMP HEATING PERFORMANCE continued
INDOOR | | | | | | | | | | | | | OUTDOOR COIL ENTERING AIR TEMPERATURES °F | | | | | | | | |
AIR | | | 17 | | | | 27 | | | | | | 37 | | | | 47 | | | | | 57 | | | | | 67 | | |
| | | | Capacity | Total | Capacity | | Total | Capacity | Total | Capacity | Total | | Capacity | Total | | Capacity | | Total |
| | | | MBtuh† | Pwr | MBtuh† | | Pwr | MBtuh† | Pwr | MBtuh† | Pwr | | MBtuh† | Pwr | | | MBtuh† | | Pwr |
EDB | | CFM | | Total | | | Int* | KW† | Total | Int* | KW† | Total | Int* | KW† | Total | Int* | KW† | Total | Int* | KW† | Total | Int* | KW† |
| | | | | 698BNX060000 Outdoor Section With FV4ANB006 Indoor Section - Low Speed | | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| | 1050 | | 13.32 | | 12.15 | 1.65 | | 17.76 | | 15.78 | | 1.76 | 22.45 | | 20.43 | 1.88 | 27.25 | | 27.25 | 2.00 | | 32.54 | | 32.54 | 2.13 | | 38.87 | 38.87 | | 2.25 |
65 | | 1350 | | 13.89 | | 12.66 | 1.67 | | 18.53 | | 16.46 | | 1.78 | 23.38 | | 21.28 | 1.89 | 28.36 | | 28.36 | 1.99 | | 34.36 | | 34.36 | 2.08 | | 37.51 | 37.51 | | 2.14 |
| 1650 | | 14.30 | | 13.04 | 1.70 | | 19.13 | | 16.99 | | 1.80 | 23.98 | | 21.82 | 1.90 | 29.23 | | 29.23 | 2.00 | | 34.58 | | 34.58 | 2.07 | | 35.47 | 35.47 | | 2.08 |
| | 1950 | | 14.90 | | 13.59 | 1.73 | | 19.49 | | 17.31 | | 1.82 | 24.51 | | 22.31 | 1.92 | 29.73 | | 29.73 | 2.02 | | 33.27 | | 33.27 | 2.05 | | 33.44 | 33.44 | | 2.05 |
| | 2250 | | 15.19 | | 13.85 | 1.76 | | 19.89 | | 17.67 | | 1.86 | 24.83 | | 22.60 | 1.95 | 30.42 | | 30.42 | 2.02 | | 32.03 | | 32.03 | 2.04 | | 32.38 | 32.38 | | 2.05 |
| | 1050 | | 12.49 | | 11.39 | 1.68 | | 16.78 | | 14.90 | | 1.80 | 21.42 | | 19.49 | 1.93 | 26.22 | | 26.22 | 2.06 | | 31.40 | | 31.40 | 2.19 | | 37.53 | 37.53 | | 2.31 |
70 | | 1350 | | 13.08 | | 11.92 | 1.70 | | 17.50 | | 15.55 | | 1.82 | 22.35 | | 20.34 | 1.93 | 27.32 | | 27.32 | 2.05 | | 32.86 | | 32.86 | 2.16 | | 37.50 | 37.50 | | 2.23 |
| 1650 | | 13.50 | | 12.31 | 1.73 | | 18.02 | | 16.00 | | 1.84 | 23.00 | | 20.93 | 1.95 | 28.05 | | 28.05 | 2.05 | | 34.03 | | 34.03 | 2.14 | | 35.81 | 35.81 | | 2.17 |
| | 1950 | | 13.82 | | 12.60 | 1.76 | | 18.43 | | 16.37 | | 1.87 | 23.46 | | 21.35 | 1.97 | 28.60 | | 28.60 | 2.07 | | 33.56 | | 33.56 | 2.13 | | 34.12 | 34.12 | | 2.14 |
| | 2250 | | 14.10 | | 12.85 | 1.80 | | 18.75 | | 16.65 | | 1.90 | 23.86 | | 21.71 | 2.00 | 29.09 | | 29.09 | 2.10 | | 32.69 | | 32.69 | 2.13 | | 33.28 | 33.28 | | 2.14 |
| | 1050 | | 11.43 | | 10.43 | 1.70 | | 15.70 | | 13.95 | | 1.84 | 20.36 | | 18.53 | 1.97 | 25.18 | | 25.18 | 2.11 | | 30.24 | | 30.24 | 2.24 | | 36.23 | 36.23 | | 2.39 |
75 | | 1350 | | 12.02 | | 10.96 | 1.73 | | 16.46 | | 14.62 | | 1.85 | 21.28 | | 19.36 | 1.98 | 26.27 | | 26.27 | 2.10 | | 31.59 | | 31.59 | 2.22 | | 37.75 | 37.75 | | 2.33 |
| 1650 | | 11.37 | | 10.37 | 1.76 | | 16.97 | | 15.07 | | 1.88 | 21.93 | | 19.96 | 1.99 | 26.98 | | 26.98 | 2.11 | | 32.80 | | 32.80 | 2.21 | | 36.11 | 36.11 | | 2.26 |
| | 1950 | | 12.73 | | 11.61 | 1.79 | | 17.36 | | 15.42 | | 1.91 | 22.40 | | 20.39 | 2.02 | 27.52 | | 27.52 | 2.13 | | 33.36 | | 33.36 | 2.22 | | 34.63 | 34.63 | | 2.23 |
| | 2250 | | 13.00 | | 11.85 | 1.83 | | 17.68 | | 15.70 | | 1.94 | 22.78 | | 20.73 | 2.05 | 27.95 | | 27.95 | 2.15 | | 33.14 | | 33.14 | 2.22 | | 33.78 | 33.78 | | 2.23 |
| | | | | | | | | | Multipliers for Determining the Performance With Other Indoor Sections | | | | | | | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| | Indoor | | | | | | | | | | Cooling | | | | | Indoor | | | | | | | | Cooling | | | |
| | Section | | | | Size | | Capacity | | | | Power | | | Section | | Size | | Capacity | | | | Power | |
CC5A/CD5AA | | | 060 | | | 1.02 | | | | 1.20 | | | | CK3BA | | 060 | | 0.98 | | | | 1.03 | | |
CC5A/CD5AB | | | 060 | | | 1.02 | | | | 1.20 | | | CK5A/CK5BA | 060 | | 0.98 | | | | 1.03 | | |
CC5A/CD5AW | | | 060 | | | 1.04 | | | | 1.19 | | | CK5A/CK5BN | 060 | | 0.99 | | | | 1.02 | | |
| | CE3AA | | | | 060 | | | 1.04 | | | | 1.18 | | | CK5A/CK5BT | 060 | | 0.98 | | | | 1.03 | | |
| | CK3BA | | | | 060 | | | 1.04 | | | | 1.18 | | | CK5A/CK5BX | 060 | | 1.00 | | | | 1.02 | | |
CK5A/CK5BA | | 060 | | | 1.04 | | | | 1.18 | | | | COILS + 355MAV060100 VARIABLE SPEED FURNACE | |
CK5A/CK5BN | | | 060 | | | 1.05 | | | | 1.17 | | | CC5A/CD5AA | 060 | | 0.98 | | | | 1.06 | | |
CK5A/CK5BT | | | 060 | | | 1.04 | | | | 1.18 | | | CC5A/CD5AB | 060 | | 0.98 | | | | 1.06 | | |
CK5A/CK5BX | | | 060 | | | 1.05 | | | | 1.17 | | | CC5A/CD5AW | 060 | | 1.00 | | | | 1.04 | | |
| FK4CNB | | | | 006 | | | 1.00 | | | | 1.00 | | | | CE3AA | | 060 | | 1.00 | | | | 1.05 | | |
| FV4ANB | | | | 006 | | | 1.00 | | | | 1.00 | | | | CK3BA | | 060 | | 1.00 | | | | 1.05 | | |
| | COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE | | CK5A/CK5BA | 060 | | 1.00 | | | | 1.05 | | |
CC5A/CD5AA | | | 060 | | | 0.97 | | | | 1.04 | | | CK5A/CK5BN | 060 | | 1.02 | | | | 1.06 | | |
CC5A/CD5AB | | | 060 | | | 0.97 | | | | 1.04 | | | CK5A/CK5BT | 060 | | 1.00 | | | | 1.05 | | |
CC5A/CD5AW | | | 060 | | | 0.98 | | | | 1.01 | | | CK5A/CK5BX | 060 | | 1.01 | | | | 1.04 | | |
| | CE3AA | | | 060 | | | 0.98 | | | | 1.02 | | | | COILS + 355MAV060120 VARIABLE SPEED FURNACE | |
| | CK3BA | | | | 060 | | | 0.98 | | | | 1.03 | | | CC5A/CD5AA | 060 | | 1.01 | | | | 1.07 | | |
CK5A/CK5BA | | | 060 | | | 0.98 | | | | 1.03 | | | CC5A/CD5AB | 060 | | 1.01 | | | | 1.07 | | |
CK5A/CK5BN | | | 060 | | | 0.99 | | | | 1.02 | | | CC5A/CD5AW | 060 | | 1.01 | | | | 1.06 | | |
CK5A/CK5BT | | | 060 | | | 0.98 | | | | 1.03 | | | | CE3AA | | 060 | | 1.00 | | | | 1.05 | | |
CK5A/CK5BX | | | 060 | | | 0.99 | | | | 1.01 | | | | CK3BA | | 060 | | 1.00 | | | | 1.06 | | |
| | COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE | | CK5A/CK5BA | 060 | | 1.00 | | | | 1.06 | | |
CC5A/CD5AA | | | 060 | | | 0.98 | | | | 1.03 | | | CK5A/CK5BN | 060 | | 1.01 | | | | 1.04 | | |
CC5A/CD5AB | | | 060 | | | 0.98 | | | | 1.03 | | | CK5A/CK5BT | 060 | | 1.00 | | | | 1.06 | | |
CC5A/CD5AW | | | 060 | | | 0.98 | | | | 1.03 | | | CK5A/CK5BX | 060 | | 1.01 | | | | 1.04 | | |
| | CE3AA | | | | 060 | | | 0.98 | | | | 1.03 | | | | | | | — | | | | — | | | | — | |
* The Btuh heating capacity values shown are net “integrated” values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.
†The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to
obtain total system kilowatts. EDB—Entering Dry Bulb
System Design
1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2.Minimum outdoor operating air temperature is 55°F (12.8°C).
3.Low-ambient operation accessory is not available.
4.Maximum outdoor operating air temperature is 125°F (51.7°C).
5.For reliable operation, unit should be level in all horizontal planes.
6.Maximum elevation of indoor coil above or below base of outdoor unit is; indoor coil above—50 ft, indoor coil below—150 ft.
7.For interconnecting refrigerant tube lengths greater than 50 ft, consult Application Guideline and Service Manual—Air Conditioners and Heat Pumps Using Puron® Refrigerant.
8.If any refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36-in. may be buried without further considerations. Do not bury lines over 36 in.
9.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
10.Must be installed with factory-supplied hard shutoff, balanced port TXV (field installed).
11.Do not apply capillary tube indoor coils to these units.
12.Factory-supplied filter drier must be installed.