HEAT PUMP HEATING PERFORMANCE continued

INDOOR

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR COIL ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

AIR

 

 

17

 

 

 

27

 

 

 

 

 

37

 

 

 

47

 

 

 

 

57

 

 

 

 

67

 

 

 

 

 

 

Capacity

Total

Capacity

 

Total

Capacity

Total

Capacity

Total

 

Capacity

Total

 

Capacity

 

Total

 

 

 

 

MBtuh†

Pwr

MBtuh†

 

Pwr

MBtuh†

Pwr

MBtuh†

Pwr

 

MBtuh†

Pwr

 

 

MBtuh†

 

Pwr

EDB

 

CFM

 

Total

 

 

Int*

KW†

Total

Int*

KW†

Total

Int*

KW†

Total

Int*

KW†

Total

Int*

KW†

Total

Int*

KW†

 

 

 

 

 

698BNX060000 Outdoor Section With FV4ANB006 Indoor Section - Low Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1050

 

13.32

 

12.15

1.65

 

17.76

 

15.78

 

1.76

22.45

 

20.43

1.88

27.25

 

27.25

2.00

 

32.54

 

32.54

2.13

 

38.87

38.87

 

2.25

65

 

1350

 

13.89

 

12.66

1.67

 

18.53

 

16.46

 

1.78

23.38

 

21.28

1.89

28.36

 

28.36

1.99

 

34.36

 

34.36

2.08

 

37.51

37.51

 

2.14

 

1650

 

14.30

 

13.04

1.70

 

19.13

 

16.99

 

1.80

23.98

 

21.82

1.90

29.23

 

29.23

2.00

 

34.58

 

34.58

2.07

 

35.47

35.47

 

2.08

 

 

1950

 

14.90

 

13.59

1.73

 

19.49

 

17.31

 

1.82

24.51

 

22.31

1.92

29.73

 

29.73

2.02

 

33.27

 

33.27

2.05

 

33.44

33.44

 

2.05

 

 

2250

 

15.19

 

13.85

1.76

 

19.89

 

17.67

 

1.86

24.83

 

22.60

1.95

30.42

 

30.42

2.02

 

32.03

 

32.03

2.04

 

32.38

32.38

 

2.05

 

 

1050

 

12.49

 

11.39

1.68

 

16.78

 

14.90

 

1.80

21.42

 

19.49

1.93

26.22

 

26.22

2.06

 

31.40

 

31.40

2.19

 

37.53

37.53

 

2.31

70

 

1350

 

13.08

 

11.92

1.70

 

17.50

 

15.55

 

1.82

22.35

 

20.34

1.93

27.32

 

27.32

2.05

 

32.86

 

32.86

2.16

 

37.50

37.50

 

2.23

 

1650

 

13.50

 

12.31

1.73

 

18.02

 

16.00

 

1.84

23.00

 

20.93

1.95

28.05

 

28.05

2.05

 

34.03

 

34.03

2.14

 

35.81

35.81

 

2.17

 

 

1950

 

13.82

 

12.60

1.76

 

18.43

 

16.37

 

1.87

23.46

 

21.35

1.97

28.60

 

28.60

2.07

 

33.56

 

33.56

2.13

 

34.12

34.12

 

2.14

 

 

2250

 

14.10

 

12.85

1.80

 

18.75

 

16.65

 

1.90

23.86

 

21.71

2.00

29.09

 

29.09

2.10

 

32.69

 

32.69

2.13

 

33.28

33.28

 

2.14

 

 

1050

 

11.43

 

10.43

1.70

 

15.70

 

13.95

 

1.84

20.36

 

18.53

1.97

25.18

 

25.18

2.11

 

30.24

 

30.24

2.24

 

36.23

36.23

 

2.39

75

 

1350

 

12.02

 

10.96

1.73

 

16.46

 

14.62

 

1.85

21.28

 

19.36

1.98

26.27

 

26.27

2.10

 

31.59

 

31.59

2.22

 

37.75

37.75

 

2.33

 

1650

 

11.37

 

10.37

1.76

 

16.97

 

15.07

 

1.88

21.93

 

19.96

1.99

26.98

 

26.98

2.11

 

32.80

 

32.80

2.21

 

36.11

36.11

 

2.26

 

 

1950

 

12.73

 

11.61

1.79

 

17.36

 

15.42

 

1.91

22.40

 

20.39

2.02

27.52

 

27.52

2.13

 

33.36

 

33.36

2.22

 

34.63

34.63

 

2.23

 

 

2250

 

13.00

 

11.85

1.83

 

17.68

 

15.70

 

1.94

22.78

 

20.73

2.05

27.95

 

27.95

2.15

 

33.14

 

33.14

2.22

 

33.78

33.78

 

2.23

 

 

 

 

 

 

 

 

 

 

Multipliers for Determining the Performance With Other Indoor Sections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

Indoor

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

Section

 

 

 

Size

 

Capacity

 

 

 

Power

 

 

Section

 

Size

 

Capacity

 

 

 

Power

 

CC5A/CD5AA

 

 

060

 

 

1.02

 

 

 

1.20

 

 

 

CK3BA

 

060

 

0.98

 

 

 

1.03

 

 

CC5A/CD5AB

 

 

060

 

 

1.02

 

 

 

1.20

 

 

CK5A/CK5BA

060

 

0.98

 

 

 

1.03

 

 

CC5A/CD5AW

 

 

060

 

 

1.04

 

 

 

1.19

 

 

CK5A/CK5BN

060

 

0.99

 

 

 

1.02

 

 

 

 

CE3AA

 

 

 

060

 

 

1.04

 

 

 

1.18

 

 

CK5A/CK5BT

060

 

0.98

 

 

 

1.03

 

 

 

 

CK3BA

 

 

 

060

 

 

1.04

 

 

 

1.18

 

 

CK5A/CK5BX

060

 

1.00

 

 

 

1.02

 

 

CK5A/CK5BA

 

060

 

 

1.04

 

 

 

1.18

 

 

 

COILS + 355MAV060100 VARIABLE SPEED FURNACE

 

CK5A/CK5BN

 

 

060

 

 

1.05

 

 

 

1.17

 

 

CC5A/CD5AA

060

 

0.98

 

 

 

1.06

 

 

CK5A/CK5BT

 

 

060

 

 

1.04

 

 

 

1.18

 

 

CC5A/CD5AB

060

 

0.98

 

 

 

1.06

 

 

CK5A/CK5BX

 

 

060

 

 

1.05

 

 

 

1.17

 

 

CC5A/CD5AW

060

 

1.00

 

 

 

1.04

 

 

 

FK4CNB

 

 

 

006

 

 

1.00

 

 

 

1.00

 

 

 

CE3AA

 

060

 

1.00

 

 

 

1.05

 

 

 

FV4ANB

 

 

 

006

 

 

1.00

 

 

 

1.00

 

 

 

CK3BA

 

060

 

1.00

 

 

 

1.05

 

 

 

 

COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE

 

CK5A/CK5BA

060

 

1.00

 

 

 

1.05

 

 

CC5A/CD5AA

 

 

060

 

 

0.97

 

 

 

1.04

 

 

CK5A/CK5BN

060

 

1.02

 

 

 

1.06

 

 

CC5A/CD5AB

 

 

060

 

 

0.97

 

 

 

1.04

 

 

CK5A/CK5BT

060

 

1.00

 

 

 

1.05

 

 

CC5A/CD5AW

 

 

060

 

 

0.98

 

 

 

1.01

 

 

CK5A/CK5BX

060

 

1.01

 

 

 

1.04

 

 

 

 

CE3AA

 

 

060

 

 

0.98

 

 

 

1.02

 

 

 

COILS + 355MAV060120 VARIABLE SPEED FURNACE

 

 

 

CK3BA

 

 

 

060

 

 

0.98

 

 

 

1.03

 

 

CC5A/CD5AA

060

 

1.01

 

 

 

1.07

 

 

CK5A/CK5BA

 

 

060

 

 

0.98

 

 

 

1.03

 

 

CC5A/CD5AB

060

 

1.01

 

 

 

1.07

 

 

CK5A/CK5BN

 

 

060

 

 

0.99

 

 

 

1.02

 

 

CC5A/CD5AW

060

 

1.01

 

 

 

1.06

 

 

CK5A/CK5BT

 

 

060

 

 

0.98

 

 

 

1.03

 

 

 

CE3AA

 

060

 

1.00

 

 

 

1.05

 

 

CK5A/CK5BX

 

 

060

 

 

0.99

 

 

 

1.01

 

 

 

CK3BA

 

060

 

1.00

 

 

 

1.06

 

 

 

 

COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE

 

CK5A/CK5BA

060

 

1.00

 

 

 

1.06

 

 

CC5A/CD5AA

 

 

060

 

 

0.98

 

 

 

1.03

 

 

CK5A/CK5BN

060

 

1.01

 

 

 

1.04

 

 

CC5A/CD5AB

 

 

060

 

 

0.98

 

 

 

1.03

 

 

CK5A/CK5BT

060

 

1.00

 

 

 

1.06

 

 

CC5A/CD5AW

 

 

060

 

 

0.98

 

 

 

1.03

 

 

CK5A/CK5BX

060

 

1.01

 

 

 

1.04

 

 

 

 

CE3AA

 

 

 

060

 

 

0.98

 

 

 

1.03

 

 

 

 

 

 

 

 

 

 

 

 

 

* The Btuh heating capacity values shown are net “integrated” values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.

The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to

obtain total system kilowatts. EDB—Entering Dry Bulb

System Design

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2.Minimum outdoor operating air temperature is 55°F (12.8°C).

3.Low-ambient operation accessory is not available.

4.Maximum outdoor operating air temperature is 125°F (51.7°C).

5.For reliable operation, unit should be level in all horizontal planes.

6.Maximum elevation of indoor coil above or below base of outdoor unit is; indoor coil above—50 ft, indoor coil below—150 ft.

7.For interconnecting refrigerant tube lengths greater than 50 ft, consult Application Guideline and Service Manual—Air Conditioners and Heat Pumps Using Puron® Refrigerant.

8.If any refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36-in. may be buried without further considerations. Do not bury lines over 36 in.

9.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

10.Must be installed with factory-supplied hard shutoff, balanced port TXV (field installed).

11.Do not apply capillary tube indoor coils to these units.

12.Factory-supplied filter drier must be installed.

—41—

Page 41
Image 41
Bryant 698B warranty System Design

698B specifications

The Bryant 698B is an advanced residential air conditioning unit known for its efficiency and reliability in delivering optimal indoor climate control. Designed for comfort and energy savings, the Bryant 698B is a notable choice for homeowners seeking high-performance cooling solutions.

One of its standout features is its impressive Seasonal Energy Efficiency Ratio (SEER) rating, which ranges from 16 to 18, depending on the specific model. This high efficiency helps to reduce energy consumption while providing consistent cooling performance, allowing homeowners to enjoy a comfortable environment without incurring high electricity bills. The unit's efficient operation is recognized by various energy efficiency certifications, helping promote a more sustainable lifestyle.

The Bryant 698B is equipped with a variable-speed compressor, which adjusts its operating speed based on the cooling needs of the home. This technology allows the system to run at lower speeds for longer periods, ensuring a more consistent temperature throughout the space and reducing wear and tear on the system. This also minimizes noise levels, making the Bryant 698B one of the quieter units available today.

In terms of build quality, the Bryant 698B features a durable steel cabinet designed to withstand harsh weather conditions. The unit is treated with a baked-on powder finish that provides corrosion resistance, ensuring its longevity even in challenging environments. Additionally, the coil is designed for easy maintenance, allowing for optimal airflow and ensuring the system runs efficiently.

Smart technology integration is another highlight of the Bryant 698B. The unit can be connected to a smart thermostat, offering homeowners remote access to control their HVAC system from their smartphones. This capability allows for more precise temperature adjustments and scheduling, contributing to enhanced energy savings and increased comfort.

The Bryant 698B also offers various customizable options, including different cooling capacities and compatibility with additional heating systems like heat pumps or gas furnaces. This versatility makes it suitable for a wide range of residential applications.

In summary, the Bryant 698B air conditioning unit stands out due to its energy efficiency, variable-speed compressor, durable construction, smart technology features, and customization options, making it an ideal choice for homeowners looking for a robust and efficient cooling solution.