Home Standby - 7kW - 12kW - 15kW
GENERATOR | Model ASPAS1BBA007 (7kW) | Model ASPAS1BBA012 (12kW) | Model ASPAS1BBA015 (15kW) |
|
|
|
|
Rated Maximum Continuous Power Capacity (LP) | 7,000 Watts* | . . . . . . .12,000 Watts* | . . . . . . .15,000 Watts* |
Rated Maximum Continuous Power Capacity (NG) | 6,000 Watts* | . . . . . . .12,000 Watts* | . . . . . . .13,000 Watts* |
Rated Voltage | 120/240 | . . . . . . . . .120/240 | . . . . . . . . .120/240 |
Rated Maximum Continuous Load Current |
|
|
|
120 Volts | 50.0 NG/58.3 LP | . . . . . 100.0 NG/100.0 LP | . . . .108.3 NG/125.0 LP |
240 Volts | 25.0 NG/29.2 LP | . . . . . .50.0 NG/ 50.0 LP | . . . . .54.2 NG/62.5 LP |
Main Line Circuit Breaker | 30 Amp | . . . . . . . . .50 Amp | . . . . . . . . .65 Amp |
Phase | .1 | . . . . . . . . . . . .1 | . . . . . . . . . . . .1 |
Number of Rotor Poles | 2 | . . . . . . . . . . . .2 | . . . . . . . . . . . .2 |
Rated AC Frequency | 60Hz | . . . . . . . . . .60Hz | . . . . . . . . . .60Hz |
Power Factor | 1 | . . . . . . . . . . . .1 | . . . . . . . . . . . .1 |
Battery Requirement (not included) | Group 26 | . . . . . . . . .Group 26 | . . . . . . . .Group 26 |
| 12 Volts and | . . . . . . . .12 Volts and | . . . . . . .12 Volts and |
| 350 | . . . . .525 | . . . . .525 |
| Amperes Minimum | . . . . .Amperes Minimum | . . . . .Amperes Minimum |
Shipping Weight (lbs.) (Includes Transfer Switch) | 375 | . . . . . . . . . . .470 | . . . . . . . . . . .487 |
Dimensions (L” x W” x H”) | 48 x 24 x | . . . . . .48 x 24 x | . . . . . .48 x 24 x |
J |
|
|
|
|
|
|
|
ENGINE | Model ASPAS1BBA007 (7kW) | Model ASPAS1BBA012 (12kW) | Model ASPAS1BBA015 (15kW) |
Type of Engine | OHVI | . . . . . . .OHVI | . . . . . . .OHVI |
Number of Cylinders | 1 | . . . . . . . . . . . . .2 | . . . . . . . . . . . . .2 |
Rated Horsepower | 14.5 @ 3,600 rpm | . . . . . .30 @ 3,600 rpm | . . . . . .30 @ 3,600 rpm |
Displacement | 410cc | . . . . . . . . . . .992cc | . . . . . . . . . . .992cc |
Cylinder Block | Aluminum w/Cast | . . . . . .Aluminum w/Cast | . . . . . .Aluminum w/Cast |
| Iron Sleeve | . . . . . . . . .Iron Sleeve | . . . . . . . . .Iron Sleeve |
Valve Arrangement | Overhead Valve | . . . . . . .Overhead Valve | . . . . . . .Overhead Valve |
Ignition System | |||
Compression Ratio | .8.6:1 | . . . . . . . . . . .9.5:1 | . . . . . . . . . . .9.5:1 |
Starter | .12 Vdc | . . . . . . . . . .12 Vdc | . . . . . . . . . .12Vdc |
Oil Capacity Including Filter | Approx. 1.5 Qts | . . . . . . .Approx. 1.7 Qts | . . . . . . .Approx. 1.7 Qts. |
Operating RPM | .3,600 | . . . . . . . . . . .3,600 | . . . . . . . . . . .3,600 |
Fuel Consumption |
|
|
|
Natural Gas cu.ft./hr. |
|
|
|
1/2 Load | . . . . . . . . . . . .66 | . . . . . . . . . . . .152 | . . . . . . . . . . . .156 |
Full Load | . . . . . . . . . . . .119 | . . . . . . . . . . . .215 | . . . . . . . . . . . .220 |
Liquid Propane ft3/hr(gal/hr) |
|
|
|
1/2 Load | . . . . . . . . . .30(0.82) | . . . . . . . . . .56(1.53) | . . . . . . . . . .58(1.58) |
Full Load | . . . . . . . . . .54(1.47) | . . . . . . . . . .76(2.08) | . . . . . . . . . .88(2.40) |
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 11 to 14 inches of water column for LP gas | |||
|
|
|
|
CONTROLS |
|
|
|
Model Switch |
|
|
|
- AutoAutomatic Start on Utility failure/7 day exerciser |
|
|
|
- Off. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Stops unit. Power is removed control and charger still operate | |||
- Manual/Test (start) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Start with starter control, unit stays on. If utility fails, transfer to load takes place. | |||
Engine Start Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cyclic cranking: 7 sec. on, 7 rest (90 sec. maximum duration) | |||
Engine | . . . . . . . . . . . . . 10 seconds |
|
|
Engine | . . . . . . . . . . . . . 1 minute |
|
|
Starter | |||
2.5 Amp Timed Trickle Battery Charger | . . . . . . . . . . . . . Standard |
|
|
Automatic Voltage Regulator w/Overvoltage Protection | . . . . . . . . . . . . . Standard |
|
|
Automatic Low Oil Pressure Shutdown | . . . . . . . . . . . . . Standard |
|
|
Overspeed Shutdown | . . . . . . . . . . . . . Standard, 72Hz |
|
|
High Temperature Shutdown | . . . . . . . . . . . . . Standard |
|
|
Overcrank Protection | . . . . . . . . . . . . . Standard |
|
|
Safety Fuse | . . . . . . . . . . . . . Standard |
|
|
|
|
|
|
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with
BS5514, ISO3046 and DIN6271). Prime (Unlimited Running Time): Unit not recommended for prime power applications. Applicable for supplying electric power in lieu of commercially purchased power. Prime power is the maximum power available at variable load. A 10% overload capacity is available for 1 hour in 12 hours. (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).
*Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F).