About Advanced Features & Operation

About Advanced Features & Operation

MEMORY BACKUP - In the event of a power loss, the thermostat will retain the stored program settings without external power or batteries.

2 STAGE OPERATION - The 2nd Stage of heat or cool is turned on when (1) the 1st Stage has been on for a minimum of two minutes, and (2) the temperature spread from the setpoint is equal to or greater than: the setpoint plus the deadband, plus 2 degrees.

Heating

Cooling

2 degrees

Dead Band

Dead Manual background

Band

2 degrees

2nd Stage

1st Stage

Heat

Cool

1st Stage

2nd Stage

turn on

turn on

Setpoint

Setpoint

turn on

turn on

MINIMUM HEAT/COOL SETPOINT DIFFERENCE - The Heat and Cool setpoints will not be allowed to come any closer to each other than the value set in Advanced Setup step

#7, on page 13. This minimum difference is enforced during Auto changeover and Program On operation.

PROGRAMMABLE FAN - If the Programmable Fan timer is set to a value other than 0:00, the fan will run for the preprogrammed amount of time, page 14, step# 9.

The Programmable Fan timer will start the fan at the top of each hour. The Programmable Fan may be active even if the thermostat mode is Off. Steps 10 & 11 restrict the hours in which Programmable Fan may operate. Step# 10, page 14 is the start time and step# 11 is the stop time. Setting the times to the same setting in both steps 10 & 11 will allow Programmable Fan to operate 24 hours a day.