G. Low Ambient Cooling Lockout Selection

The Low Ambient Cooling Lockout feature will lock out cool- ing mode if the outdoor-air temperature is below the lockout cooling temperature (user-con®gured).

NOTE: This con®guration is not available if DIP switch C (Re- mote Room Sensor) is set to ON or if the outdoor-air sensor is in error.

The default is OF (disabled). The lockout temperature can be set to OF (disabled) or 20 to 60 F in 5-degree increments (en- abled). To con®gure the selection, press the Program button in the con®guration mode. Use the Up and Down buttons to increase or decrease the setting.

V. CHECK THERMOSTAT OPERATION

Perform the following procedure to check thermostat operation:

1.Press the Hold button. This will prevent the set point from changing until the desired time and temperature schedule is entered.

2.Press the Fan button to switch the fan annunciator from AUTO to ON. The fan should run continuously. Check fan operation. Press the fan button again to switch back to AUTO.

3.Press the mode button repeatedly until HEAT is dis- played in the mode annunciator. Press the Up button until the set point reads 10 degrees above room tem- perature. The heating system should begin to operate within 5 minutes.

4.Press the mode button repeatedly until COOL is dis- played in the mode annunciator. Press the Down button until the set point reads 10 degrees below room tem- perature. The cooling system should begin to operate within 5 minutes.

VI. SELECT THERMOSTAT OPERATION SETTINGS

heating set point). If COOL is selected, the thermostat will only enter cooling mode (if the room temperature is above the cooling set point). If AUTO is selected, the thermostat will enter heating or cooling mode based on the room tempera- ture and the heating and cooling set points. Heat pumps also have an EHEAT selection. If EHEAT is selected, the heat pump will use the second stage of heating to provide heat when needed. The annuciator for each selection will be displayed on the thermostat when selected.

II.FIVE-MINUTE COMPRESSOR SHORT-CYCLE PROTECTION

The timer prevents the compressor from starting until it has been off for at least 5 minutes. The short-cycle protection func- tion can be disabled (for one cycle only) by simultaneously pressing the Fan button and the Up button.

III. FIFTEEN-MINUTE CYCLE TIMER

The cycle timer prevents the start of a heating or cooling cycle until at least 15 minutes after the last start of the same cycle. This function keeps the equipment from being cycled more than 4 times in one hour. The cycle timer can be disabled (for one cycle only) by either changing the temperature set point or by simultaneously pressing the Fan button and the Up button.

IV. FIFTEEN-MINUTE STAGING TIMER

When multi-stage heating or cooling is used, the staging timer prevents any higher stage from energizing until at least 15 minutes has passed from the start of the previous stage. The timer is disabled if the temperature demand is greater than 5 degrees.

V. TWO-MINUTE MINIMUM ON TIME

In normal operation, when a stage is energized, it must re- main on for at least 2 minutes.

Thermostat operation should be con®gured. Set the Fan and Mode con®gurations to their desired settings. Press the Up and Down buttons to select the desired comfort temperature.

NOTE: Daily schedules can be programmed by the installer or the user. A detailed explanation of the schedule program- ming is in the Owner's Guide. If the daily schedules of the thermostat are being con®gured, refer to the thermostat own- er's guide literature.

VII. FINAL CHECKLIST

1.Put away tools and instruments. Clean up debris and packaging.

2.Review Owner's Guide with occupant or owner.

3.Leave Owner's Guide with occupant or owner.

OPERATION

I. HOLD, FAN, AND MODE BUTTON OPERATION

Pressing the Hold button disables the time and temperature schedule and holds the current desired temperature set point. When a Hold is active, the HOLD annunciator is displayed on the thermostat screen. To release the Hold, press the Hold button a second time.

The Fan button selects fan operation. When the fan is set to ON, the fan will run continuously. When the fan is set to AUTO, the fan will run during heating and cooling operation only.

The Mode button selects the operating mode of the thermo- stat. If OFF is selected, the thermostat will not enter heating or cooling mode. If HEAT is selected, the thermostat will only enter heating mode (if the room temperature is below the

Ð5Ð

VI. HEATING/COOLING SET POINT MINIMUM DIFFERENCE

A minimum difference of 3 degrees is enforced between the heating and cooling set points. The thermostat will not allow the set points to be set within 3 degrees of each other.

VII. AUTO-CHANGEOVER TIMER

When the auto-changeover mode is selected, the thermostat will not change from heating to cooling or cooling to heating until an opposite demand has existed for a minimum of 10 minutes. The timer is disabled if the heating or cooling set point is changed.

VIII. POWER-ON THERMOSTAT CHECK

When power is applied to the thermostat, all possible display annunciators are turned on for a few seconds. The thermo- stat then indicates the current mode and con®guration infor- mation with a 2-digit code. The following codes can be dis- played: AC Ð single-speed air conditioner, HP Ð single- speed heat pump, A2 Ð two-speed air conditioner, and H2 Ð two-speed heat pump.

IX. ERROR CODES

The thermostat will display the following error codes if er- rors are detected:

E1 Ð If the thermostat cannot properly read room tempera- ture, the thermostat will display an E1 and all outputs (ex- cept the fan if on), will be deenergized.

E2 Ð If the AC line voltage drops below the minimum level, all outputs are deenergized and the thermostat will display an E2. The E2 error will remain until proper line voltage has

Page 5
Image 5
Bryant TSTATBBPCM01-A Check Thermostat Operation, VI. Select Thermostat Operation Settings, TWO-MINUTE Minimum on Time