Alpine Specifications
|
| Input (MBH) |
| Output | Net | AFUE | Boiler Water | Heat Trans. | Shipping | |
|
|
|
| |||||||
Model No. | Minimum | Maximum | I=B=R | Volume | Area | Weight | ||||
(MBH) | (%) | |||||||||
| to 2k ft. | (MBH) | (gallons) | (sq. ft.) | (pounds) | |||||
|
|
| ||||||||
|
|
|
|
|
|
| ||||
ALP080 | 16 | 27 | 80 | 73 | 63 | 95 | 0.6 | 0.6 | 137 | |
ALP105 | 21 | 35 | 105 | 96 | 83 | 95 | 0.7 | 0.7 | 155 | |
ALP150 | 30 | 50 | 150 | 137 | 119 | 95 | 1.3 | 1.3 | 182 | |
ALP210 | 42 | 70 | 210 | 193 | 168 | 95 | 1.7 | 1.7 | 206 | |
ALP285 | 57 | 57 | 285 | 263 | 229 | 95 | 2.4 | 2.4 | 256 | |
ALP399 | 80 | 80 | 399 | 377* | 328 | 94.1/94.5** | 3.4 | 3.4 | 304 | |
ALP500 |
|
| – Call for product availability and additional information – |
|
| |||||
NOTES: DOE Heating Capacity (ALP080 through ALP285); Gross Output (ALP399) | *Gross output | ** Thermal/combustion efficiency |
| |||||||
Maximum Working Pressure - Water: |
|
|
| |||||||
Maximum Allowable Temperature = 210˚ F |
|
|
|
|
|
|
| |||
Boilers shipped set for natural gas; field adjustment for LP (see instruction manual) |
|
|
|
| ||||||
For elevations above 2000 feet, reduce ratings four percent (4%) per 1000 feet above sea level |
|
|
|
|
Alpine Dimensions
Model | A | B | C | D | E | F | G | H | J | L | M | O | P | Q |
No. | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) | (in.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ALP080 | 1/2 | 1 | 1 | * | 8 | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ALP105 | 14 | 1/2 | 1 | 1 | * | 8 | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ALP150 | 1/2 | 1 | 1 | * | 8 | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ALP210 | 1/2 | 1 | 1 | * | 8 | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ALP285 | 18 | 3/4 | * | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ALP399 | 1 | * | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Factory provided socket end compression pipe joining clamp for 3/4” schedule 40 PVC pipe
Alpine Intake / Vent Sizes
Model | Intake | Vent | Max |
No. | Size | Size | Length |
|
|
|
|
ALP080 | 3” | 3” | 60’ |
|
|
|
|
ALP105 | 3” | 3’ | 60’ |
|
|
|
|
ALP150 | 4” | 3” | 60’ |
|
|
|
|
ALP210 | 4” | 3” | 60’ |
|
|
|
|
ALP285 | 4” | 4” | 60’ |
|
|
|
|
ALP399 | 4” | 4” | 60’ |
|
|
|
|
Max length in equivalent feet for each run is 60 equivalent feet of intake & 60 equivalent feet vent length
Maximum Vent Lengths
| A |
| Low Voltage |
|
Line Voltage |
| L |
| |
| Knockouts (24V) | |||
Knockouts (115V) |
|
| ||
|
|
|
| |
One handle on |
|
|
|
|
ALP80 & 105, Two |
|
|
|
|
handles on all |
|
| F |
|
other models |
|
|
| |
|
| (Gas valve inlet) |
| |
|
|
|
| |
G |
|
|
|
|
(Return tapping) |
|
| H |
|
|
|
|
| |
|
|
| (Supply tapping) | |
|
|
| 3/4” FPT | M |
|
|
|
| |
|
|
| relief/drain |
|
|
|
| tapping | N |
|
|
|
| |
|
|
| O |
|
P |
|
| J |
|
|
| (Condensate |
| |
|
|
|
| |
|
|
| trap drain) |
|
Q |
| B |
|
|
| C E |
|
| |
| D |
|
| |
|
|
|
|
Alpine
# of 90° Elbows | 2 | 4 | 6 | 8 | 10 | 12 | NOTE: Snorkels are approved for use with PVC venting. | |
Intake & vent lengths combined. 90° = 5 equivalent feet. | ||||||||
|
|
|
|
|
|
| ||
Combined Intake/Vent - Feet of Pipe | 110’ | 100’ | 90’ | 80’ | 70’ | 60’ | Terminals do not count towards vent feet length | |
|
|
|
|
|
|
|
|
| www.burnham.com |
| |
Pub. | © 2008 U.S. Boiler Company, Inc. - Lancaster, PA | Printed in the U.S.A. | |
Phone: | |||
|
| ||
| www.burnham.com |
|