Burnham Gas-Fired Alpine Specifications, Alpine Dimensions, Alpine Intake / Vent Sizes, I=B=R

Models: Gas-Fired Condensing Stainless Steel

1 4
Download 4 pages 3.41 Kb
Page 4
Image 4
Alpine Specifications

Alpine Specifications

 

 

Input (MBH)

 

Output

Net

AFUE

Boiler Water

Heat Trans.

Shipping

 

 

 

 

Model No.

Minimum

Maximum

I=B=R

Volume

Area

Weight

(MBH)

(%)

 

to 2k ft.

2-7k ft.

0-7k ft.

(MBH)

(gallons)

(sq. ft.)

(pounds)

 

 

 

 

 

 

 

 

 

 

ALP080

16

27

80

73

63

95

0.6

0.6

137

ALP105

21

35

105

96

83

95

0.7

0.7

155

ALP150

30

50

150

137

119

95

1.3

1.3

182

ALP210

42

70

210

193

168

95

1.7

1.7

206

ALP285

57

57

285

263

229

95

2.4

2.4

256

ALP399

80

80

399

377*

328

94.1/94.5**

3.4

3.4

304

ALP500

 

 

– Call for product availability and additional information –

 

 

NOTES: DOE Heating Capacity (ALP080 through ALP285); Gross Output (ALP399)

*Gross output

** Thermal/combustion efficiency

 

Maximum Working Pressure - Water: ALP080-285=30PSI; ALP399=50PSI; 80PSI optional on all models

 

 

 

Maximum Allowable Temperature = 210˚ F

 

 

 

 

 

 

 

Boilers shipped set for natural gas; field adjustment for LP (see instruction manual)

 

 

 

 

For elevations above 2000 feet, reduce ratings four percent (4%) per 1000 feet above sea level

 

 

 

 

Alpine Dimensions

Model

A

B

C

D

E

F

G

H

J

L

M

O

P

Q

No.

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

(in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALP080

12-9/16

5-5/8

7-5/16

9-5/16

5-15/16

1/2

1

1

*

8

32-3/16

16-11/16

12-1/2

4-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALP105

14

5-13/16

7-5/16

10-3/4

5-15/16

1/2

1

1

*

8

32-3/16

16-11/16

12-1/2

4-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALP150

19-11/16

5-13/16

7-5/16

16-7/16

5-15/16

1/2

1

1

*

8

32-3/16

16-11/16

12-1/2

4-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALP210

23-15/16

5-13/16

7-5/16

17-1/8

5-15/16

1/2

1

1

*

8

32-3/16

16-11/16

12-1/2

4-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALP285

21-13/16

7-5/16

14-1/8

18

12-1/4

3/4

1-1/4

1-1/4

*

8-5/16

43-7/16

17-5/16

12-3/16

4-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALP399

28-7/8

6-3/16

13-1/16

23-3/4

15-13/16

1

1-1/2

1-1/2

*

8-5/16

43-7/16

17-5/16

12-3/16

4-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Factory provided socket end compression pipe joining clamp for 3/4” schedule 40 PVC pipe

Alpine Intake / Vent Sizes

Model

Intake

Vent

Max

No.

Size

Size

Length

 

 

 

 

ALP080

3”

3”

60’

 

 

 

 

ALP105

3”

3’

60’

 

 

 

 

ALP150

4”

3”

60’

 

 

 

 

ALP210

4”

3”

60’

 

 

 

 

ALP285

4”

4”

60’

 

 

 

 

ALP399

4”

4”

60’

 

 

 

 

Max length in equivalent feet for each run is 60 equivalent feet of intake & 60 equivalent feet vent length

Maximum Vent Lengths

 

A

 

Low Voltage

 

Line Voltage

 

L

 

 

Knockouts (24V)

Knockouts (115V)

 

 

 

 

 

 

One handle on

 

 

 

 

ALP80 & 105, Two

 

 

 

 

handles on all

 

 

F

 

other models

 

 

 

 

 

(Gas valve inlet)

 

 

 

 

 

G

 

 

 

 

(Return tapping)

 

 

H

 

 

 

 

 

 

 

 

(Supply tapping)

 

 

 

3/4” FPT

M

 

 

 

 

 

 

 

relief/drain

 

 

 

 

tapping

N

 

 

 

 

 

 

 

O

 

P

 

 

J

 

 

 

(Condensate

 

 

 

 

 

 

 

 

trap drain)

 

Q

 

B

 

 

 

C E

 

 

 

D

 

 

 

 

 

 

16-11/16”

Alpine

# of 90° Elbows

2

4

6

8

10

12

NOTE: Snorkels are approved for use with PVC venting.

Intake & vent lengths combined. 90° = 5 equivalent feet.

 

 

 

 

 

 

 

Combined Intake/Vent - Feet of Pipe

110’

100’

90’

80’

70’

60’

Terminals do not count towards vent feet length

 

 

 

 

 

 

 

 

 

www.burnham.com

 

Pub. HYDL04081-25Ms

© 2008 U.S. Boiler Company, Inc. - Lancaster, PA

Printed in the U.S.A.

Phone: 1-888-432-8887

 

 

 

www.burnham.com

 