H.Operating Instructions
1.Follow Operating Instructions to place boiler in operation. See Figure 22.
2.Electronic Ignition Modules with LED indicators. Table 10
Figure 23: LED Locations
TABLE 11: Yellow LED Flame Codes
numbers in the wiring ladder diagrams. The yellow LED indicates the status of the flame, see Table 11. The green LED indicates the status of the system, see Table 12. See Figure 23 for LED locations. See Figure 24 for Troubleshooting Guide.
Table 10: Ignition Module Terminal
Cross-Reference
Ignition Module | Wiring Ladder Diagram |
Terminal Designation | Terminal Number |
MV | 1 |
MV/PV | 2 |
|
|
PV | 3 |
|
|
GND | 4 |
|
|
24V (GND) | 5 |
|
|
24V | 6 |
|
|
SPARK | 9 |
Yellow LED | Indicates | Recommended Service Action | |
Flash Codea | |||
Heartbeat | Normal Flame Signal | N/A | |
|
|
| |
| Weak Flame Signal - |
| |
| System will operate reliably but flame signal is |
| |
2 | less than desired. | Perform routine maintenance to | |
Note: This indication may flash temporarily | assure optimum flame signal. | ||
| |||
| during or shortly after lightoff on some appli- |
| |
| cations. |
| |
| Marginal Flame Signal (less than 1.1 µA) - |
| |
| System may not operate reliably over time. | Check gas supply, pilot burner, flame | |
| Service call recommended. | ||
1 | sense wiring, contamination of flame | ||
Note: This indication may flash temporarily | |||
| rod, burner ground connection. | ||
| during or shortly after lightoff on some appli- | ||
|
| ||
| cations. |
| |
| No Flame or Flame Signal - |
| |
OFF | Below minimum threshold for system opera- | N/A | |
| tion. |
|
aFlash Code Descriptions
-Heartbeat: Constant ½ second bright, ½ second dim cycles.
-The flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats sequence.