Cabletron Systems KBU64 Rackmount user manual Configuration Using a Manager Card, Xxx

Models: KBU64 Rackmount

1 26
Download 26 pages 33.81 Kb
Page 19
Image 19

KBU64 Rackmount User Manual

4.2 Configuration Using a Manager Card

With the Manager Card pair and all KBU card pairs fitted the first task is to set the individual KBU 64 poll numbers. Once all the units are installed and a suitable terminal connected to the rack manager card command port, the lockout switches should be set to disable access to all the KBU 64s except one (for the sake of convenience it is better to configure the left most KBU 64 first). The individual poll address can then be set by typing the following commands:-

1> SET POLL xxx[CR]

where

xxx

represents the unique address in the range 001 to

999

 

 

Next, the KBU 64 card needs to be set for polled mode by typing

1> SET CONSOLE POLL[CR]

To check that the KBU 64 is responding, type

1> POLL xxx [CR]

where

xxx

represents the address that you have just set

The lockout switch for this KBU 64 should then be set to disable the KBU 64 and the next KBU 64 can be programmed by enabling via the lockout switches etc. etc.

Once all the KBU 64s have been programmed, the lockout switches must be set to enable ALL the KBU 64s.

4–2

80-10100001-09

Page 19
Image 19
Cabletron Systems KBU64 Rackmount user manual Configuration Using a Manager Card, Xxx