30XA080-350 Remote Cooler Accessory 60 Hz

Installation Instructions

Part Numbers 00EFN900003000A, 00EFN900003100A

CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16 Cooler and Economizer Removal. . . . . . . . . . . . . . . . . 4

Remote Cooler and Economizer Installation. . . . . 10

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location. Only trained, qualified installers and service technicians should install, start-up, and service this equipment.

When working on air-conditioning equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling equipment.

Be sure power to equipment is shut off before performing maintenance or service. Lock out and safety-tag all disconnects.

GENERAL

The remote cooler accessory allows for the indoor reloca- tion of the cooler on 30XA080-350 units as another means of freeze protection. When the cooler is located in a heated space, an anti-freeze solution is not needed and the performance degradation associated with antifreeze solution can be avoided. Maximum separation of the 30XA base unit and cooler is limited to 50 lineal ft (15.25 m) or 75 equivalent ft (22 m) of piping. For more information, refer to the Carrier Piping De- sign manual.

The liquid and economizer lines between the exterior- installed unit and the remote, interior-installed cooler must have pressure relief devices installed in accordance with ASHRAE 15 (American Society of Heating, Refrigeration, and Air Conditioning Engineers) and local codes.

Units to be modified for a remote cooler application must have the following options:

Factory-installed suction service valve option.

Condenser coil type:

Aluminum fin and copper tube

Pre-coat aluminum fin and copper tube

E-coat aluminum fin and copper tube

Copper fin and copper tube

E-coat copper fin and copper tube

NOTE: The microchannel heat exchanger option can NOT use the remote cooler accessory.

The application is limited to the following constraints:

Operating chilled water temperature is between 40 and 55 F (4.4 and 12.8 C). When the remote cooler is applied, the cooler heaters will not function, so it is critical to maintain the water temperature above the freezing point at all times. If the water temperature falls below the freezing point, the cooler does not have protection to keep the water from freezing.

The interior space temperature where the cooler will be installed must be maintained at a minimum of 50 F (10 C).

Underground refrigerant piping is NOT permitted for this application.

See Table 1 for accessory package usage and see Table 2 for accessory package contents. In addition to the parts supplied with each accessory package, the following material must be field-supplied:

Refrigerant grade liquid and suction line copper piping for 30XA080-120: circuits A and B and 30XA140-160: circuit B (length determined by installation). See Tables 3A and 3B for pipe sizes.

Schedule 40 steel pipe for 30XA140-160: circuit A and

30XA180-350: circuits A and B (length determined by installation). See Tables 3A and 3B for pipe sizes.

350 psig pressure relief valves and fittings (2 per circuit)

Suction line tubing insulation (length determined by installation)

Economizer line tubing insulation (length determined by installation)

1/2 in. strain relief (2)

Conduit (length determined by installation)

ASME (American Society of Mechanical Engineers) B16.9 stub end (4 in. [102 mm]), Schedule 40 Steel (one needed for 30XA140-160, two needed for 30XA180-350)

ASME B16.5 Class 600 pipe flange (4 in. [102 mm]) with field-modified extra mounting hole (one needed for 30XA260-300, two needed for 325, 350)

Flange mounting hardware

Extra flange gaskets (if necessary)

The 30XA units use R-134a refrigerant. No other refriger- ant may be used in this system. Suction tubing design pres- sure is 220 psig (1517 kPa). Economizer and liquid tubing design pressure is 350 psig (2413 kPa). Failure to use gage set, hoses, and recovery systems designed to handle R-134a refrigerant may result in personal injury and equip- ment damage. If unsure about equipment, consult the equipment manufacturer.

Table 1 — Accessory Package Usage

30XA UNIT SIZE

PACKAGE REQUIRED

080-200

00EFN900003000A

220-350

00EFN900003100A

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

2

Catalog No. 04-53300012-01

Printed in U.S.A.

Form 30XA-7SI

Pg 1

1-07

Replaces: New

Tab

5c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 1
Image 1
Carrier 00EFN900003000A installation instructions Installation Instructions

00EFN900003000A specifications

The Carrier 00EFN900003000A is a cutting-edge heating, ventilation, and air conditioning (HVAC) unit designed to meet the varying demands of both residential and commercial applications. Its innovative features and advanced technologies make it a leader in energy efficiency and performance.

One of the main features of the Carrier 00EFN900003000A is its variable-speed compressor, which allows for precise temperature control. This technology enables the unit to adjust its output based on the specific cooling or heating needs of the space, ensuring optimal comfort and minimizing energy consumption. The variable-speed operation results in quieter performance as the system smoothly ramps up or down rather than operating at a constant speed.

This model is equipped with advanced refrigerant technology, utilizing environmentally friendly R-410A refrigerant. This hydrofluorocarbon (HFC) refrigerant is designed to reduce ozone depletion potential while maintaining high energy efficiency. The Carrier 00EFN900003000A includes high-efficiency coils that enhance heat exchange, boosting the system's overall performance and durability.

Another notable characteristic of the Carrier 00EFN900003000A is its integrated smart technology. This unit can be connected to modern smart home systems, allowing users to monitor and control their HVAC system from anywhere via smartphone applications. The ability to receive alerts for maintenance needs and system performance helps ensure that the unit operates at peak efficiency over its lifespan.

Design-wise, the Carrier 00EFN900003000A boasts a compact and lightweight structure, making it suitable for various installation scenarios, from tight residential spaces to larger commercial environments. Its robust build quality ensures longevity and reliability, even in harsh weather conditions.

Furthermore, the unit features a user-friendly interface that simplifies operation and programming. With programmable settings and adjustable fan speeds, users can easily customize their comfort levels while maximizing energy efficiency.

In summary, the Carrier 00EFN900003000A represents a significant advancement in HVAC technology, offering variable-speed operation, eco-friendly refrigerants, smart connectivity, and user-centric design. This model stands out as an ideal choice for consumers seeking energy efficiency and superior comfort in their indoor environments.