CUT ALONG DOTTED LINECUT ALONG DOTTED LINE

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

FIELD WIRING DIAGRAM

NOTES:

1.Factory wiring is in accordance with National Electrical Code (NEC). Field modi®ca- tions or additions must be in compliance with all applicable codes.

2.Wiring for main ®eld power supply must be rated 75° C minimum. Use copper for all units. Maximum incoming wire size for each terminal block is 500 kcmil.

3.Power for control circuit should be supplied from a separate source through a ®eld supplied fused disconnect with 30 amp maximum protection for 115 volt control circuits and 15 amp maximum protection for 230 volt control circuit. Connect control circuit power to terminals 1 and 2 of TB4. Connect neutral side of supply to terminal 2 of TB4. Control circuit conductors for all units must be coppr only. 380/415 control power wired at factory. Requires ®eld supplied neutral connection.

4.Terminals 13 and 14 of TB2 are for ®eld external connection for remote ON-OFF. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.

5.Terminals 11 and 12 of TB2 are for chilled water ¯ow switch (CWFS) and chilled water pump interlock (CWPI) functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.

6.Terminals T3 and T4 on relay board are for chilled water pump. The maximum load allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush at 115 or 230 volt.

 

 

LEGEND

CCN

Ð Carrier Comfort Network

CWFS

Ð Chilled Water Flow Switch

CWP

Ð Chilled Water Pump

CWPI

Ð Chilled Water Pump Interlock

EQUIP

Ð

Equipment

GND,GRD

Ð

Ground

TB

Ð

Terminal Block

Field Power Wiring

Field Control Wiring

Factory Installed Wiring

11

Page 11
Image 11
Carrier 30GX080-265 manual Field Wiring Diagram