38CKC(Q), 38CMC, 38BRC Split-System Air Conditioner
Visit www.carrier.com
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor- oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the
Before installing, modifying, or servicing system, main elec- trical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.
1. Locate unit away from windows.
A97005
Fig. 1ÐSplit-System Air Conditioner
7.Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with the tubing. (See Fig. 2.)
8.Ensure that tubing insulation is pliable and completely sur- rounds vapor tube.
9.When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 2.)
10.Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
When outdoor unit is connected to
INSTALLATION
2.Ensure that vapor and liquid tube diameters are appropriate to capacity of unit. (See Model Specific Instructions for proper tube sizing.)
3.Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4.Leave some slack between structure and unit to absorb vibration.
Step 1ÐCheck Equipment and Jobsite
INSPECT EQUIPMENT Ð If shipment is damaged or incom- plete, file claim with shipping company prior to installation. Locate unit rating plate on unit service panel. It contains informa- tion needed to properly install unit. Check rating plate to be sure unit matches job specifications.
Step 2ÐInstall on a Solid, Level Mounting Pad
5.When passing refrigerant tubes through the wall, seal opening with RTV or other pliable
6.Avoid direct tubing contact with water pipes, ductwork, floor joists, wall studs, floors, and walls.
If conditions or local codes require the unit be attached to pad, use tiedown bolts to fasten through knockouts provided in unit base pan. Refer to Fig. 3 for pad dimensions and dimensions needed to mount unit to pad.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.