LOCK NUT

TUBING

MARK ON LOCK NUT

AND TUBE

A92122

Fig. 7ÐProper Marking of Valve Assembly (38CKQ)

ELECTRICAL JUNCTION

ELECTRICAL COIL

VALVE

FLOW ARROW

STRAIGHT 3/8 IN. STUD

5. Wire solenoid coil into system control circuit.

Step 8ÐMake Electrical Connections

To avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed.

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.

NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage or phase imbalance (3 phase) may fluctuate above or below permissible limits.

NOTE: Use copper wire only between disconnect switch and unit.

NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.

ROUTE GROUND AND POWER WIRES Ð Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning can result in an electric shock, fire, or death.

CONNECT GROUND AND POWER WIRES Ð Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 9.

NOTE: System flow direction must match arrow on bottom of body.

A87044

Fig. 8ÐSolenoid Valve Installation

Wiring must comply with local codes and NEC requirements, if a field-supplied control power source is needed when adding solenoid.

1.

Remove coil liquid connection cap and discard.

2.

Mount solenoid valve on liquid tube, making sure valve flow

 

arrow points toward indoor coil. Mount valve in any position

 

except valve body at top and electric coil at bottom. (See Fig.

 

8.) Solenoid valve is to be installed a maximum of 2 ft from

DISCONNECT

PER N.E.C. AND/OR LOCAL CODES

FIELD POWER

WIRING

3 PHASE ONLY

FIELD GROUND

WIRING

CONTACTOR

BLUE

GROUND

LUG

A94025

indoor coil.

Avoid valve damage while brazing by wrapping valve with a heat-sinking material such as a wet cloth.

3.Braze valve onto end of liquid tube using silver bearing or non-silver bearing brazing material. Consult local code re- quirements.

4.Braze flare adapter onto outlet end of solenoid valve.

Fig. 9ÐLine Power Connections

CONNECT CONTROL WIRING Ð Route 24-v control wires through control wiring grommet and connect leads to control wiring. (See Fig. 10.)

Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.

Use furnace transformer, fan coil transformer, or accessory trans- former for control power, 24-v/40-va minimum.

4

Page 4
Image 4
Carrier 38CKC(Q) instruction manual ÐProper Marking of Valve Assembly 38CKQ, ÐMake Electrical Connections

38CKC(Q) specifications

The Carrier 38CKC(Q) is a highly efficient ductless air conditioning system designed to provide superior comfort while minimizing energy consumption. This innovative model is especially popular for both residential and commercial applications. With its sleek design and advanced features, the 38CKC(Q) stands out in the competitive landscape of HVAC technologies.

One of the main features of the Carrier 38CKC(Q) is its inverter-driven compressor. This technology allows the system to adjust its cooling output according to the home’s demands, resulting in enhanced energy efficiency. The inverter system operates quietly and reduces wear and tear on components, leading to longer lifespan and lower maintenance costs.

The 38CKC(Q) also boasts high Seasonal Energy Efficiency Ratio (SEER) ratings, reflecting its ability to deliver cooling with significantly reduced energy consumption. This not only makes it environmentally friendly but also reduces utility bills, appealing to homeowners and business owners focused on sustainability.

Another notable characteristic is the system's multi-zone capability, allowing it to efficiently cool multiple rooms or areas. This is particularly advantageous for larger spaces where consistent and customizable comfort levels are desired. Each room can be controlled individually, ensuring that occupants can set preferred temperatures without affecting the entire system.

The installation of the Carrier 38CKC(Q) is relatively straightforward, often requiring minimal modification to existing structures. Its compact design allows for flexible placement options, making it suitable for various layouts and architectural styles.

Moreover, the unit is equipped with advanced filtration technology, enhancing indoor air quality by capturing dust, allergens, and pollutants. This feature is essential for homeowners concerned with health and wellness, providing a cleaner and fresher indoor environment.

Additionally, the Carrier 38CKC(Q) includes smart technology integration, allowing users to control the system remotely via mobile applications. This feature enhances convenience and offers the ability to monitor energy usage, aligning with modern smart home trends.

In summary, the Carrier 38CKC(Q) is a versatile and efficient ductless air conditioning solution, featuring inverter-driven technology, high SEER ratings, multi-zone capabilities, and smart integration. Its design and functionality make it an ideal choice for anyone seeking reliable and effective cooling solutions.