Carrier 38EYA Make Electrical Connections, Compressor Crankcase Heater, Start-Up

Models: 38EYA

1 16
Download 16 pages 30.44 Kb
Page 6
Image 6

DISCONNECT

PER N.E.C. AND/OR

LOCAL CODES

CONTACTOR

FIELD POWER

WIRING

3 PHASE ONLY

BLUE

FIELD GROUND

WIRING

GROUND

LUG

A94025

Fig. 11—Line Power Connections

1.Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.

2.Close service valves and shut off vacuum pump.

3.Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.

4.Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.

5.Repeat this procedure as indicated in Fig. 10. System will then be free of any contaminants and water vapor.

FINAL TUBING CHECK

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

Step 10—Make Electrical Connections

To avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed.

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company to correct improper voltage. See unit rating plate for recommended circuit protection device.

NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage or phase imbalance (3-phase) may fluctuate above or below permissible limits.

NOTE: Use copper wire only between disconnect switch and unit.

NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.

ROUTE GROUND AND POWER WIRES

Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning can result in an electric shock, fire, or death.

CONNECT GROUND AND POWER WIRES

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 11.

CONNECT CONTROL WIRING

Route 24-v control wires through control wiring grommet and connect leads to control wiring. (See Fig. 12-17.)

Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from incoming power leads.

Use furnace transformer, fan coil transformer, or accessory trans- former for control power, 24-v/40-va minimum.

NOTE: Use of available 24-v accessories may exceed the mini- mum 40-va power requirement. Determine total transformer load- ing and increase the transformer capacity or split the load with an accessory transformer as required.

FINAL WIRING CHECK

IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.

Step 11—Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.

A crankcase heater is required in long-line applications (tubing greater than 50 ft. or elevation greater than 20 ft. between indoor and outdoor units). Refer to Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps Using Puron® Refrigerant.

Step 12—Install Electrical Accessories

Refer to the individual instructions packaged with kits or acces- sories when installing.

Step 13—Start-Up

To prevent compressor damage or personal injury, observe the following:

Do not overcharge system with refrigerant.

Do not operate unit in a vacuum or at negative pressure.

Do not disable low-pressure switch

In scroll compressor applications:

• Dome temperatures may be hot

To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant.

6

Page 6
Image 6
Carrier 38EYA Make Electrical Connections, Compressor Crankcase Heater, Install Electrical Accessories, Start-Up

38EYA specifications

The Carrier 38EYA is a high-efficiency, ducted air conditioning system that stands out in the HVAC industry for its blend of advanced technology, reliable performance, and energy-saving capabilities. Designed for residential applications, the 38EYA model showcases Carrier’s commitment to innovation and comfort.

One of the key features of the Carrier 38EYA is its outstanding SEER (Seasonal Energy Efficiency Ratio) rating, often exceeding 16, which underscores its energy efficiency. This high rating means that the unit consumes less electricity, leading to lower utility bills while maintaining a comfortable indoor climate. The system is equipped with a variable-speed compressor that adjusts its output to meet the cooling demands of the space, providing precise temperature control while minimizing energy consumption.

In addition to its efficiency, the 38EYA includes advanced refrigerant technology. Utilizing R-410A, a more environmentally friendly refrigerant, this unit contributes to reduced global warming potential compared to older refrigerants. The Carrier 38EYA also features a corrosion-resistant steel cabinet, ensuring durability and longevity in varying weather conditions.

User-friendly operation is enhanced through the optional smart thermostat, which allows homeowners to control their cooling system remotely. This integration with smart technology provides convenience and helps optimize energy use, further enhancing savings on energy costs. Additionally, the whisper-quiet operation of the system ensures that homeowners can enjoy a peaceful environment without the distraction of loud machinery.

Furthermore, the Carrier 38EYA incorporates a multi-stage filtration system that improves indoor air quality by capturing dust, allergens, and other pollutants. This feature is particularly beneficial for households with allergy sufferers or pets.

Overall, the Carrier 38EYA represents a blend of energy efficiency, advanced technology, and user-friendly features, making it a top choice for homeowners seeking a reliable and effective home cooling solution. Its commitment to sustainability, combined with optimal performance, positions the 38EYA as a leading option in modern air conditioning systems, ensuring comfort and satisfaction for years to come.