PISTON
RETAINER
PISTON
RING
PISTON
PISTON
BODY
FIELD
CONNECTION
STRAINER
FLARE
ADAPTOR
LIQUID LINE STRAINER
APPROX. 2” LONG
STRAINER LABEL (AFFIX TO LIQ. LINE
NEAR STRAINER LOCATION)
A95615
Fig. 2ÐAccurater Components
existing
NOTE: FK4 fan coils are equipped with an
Step 4ÐInstall AccuRater® Piston and Ring
ACCURATER PISTON
1.If unit is to be installed with a piston metering device, check indoor piston to see if it matches required piston on outdoor unit rating plate. If it does not match, replace with piston shipped with outdoor unit. The piston shipped with outdoor unit is correct for any approved indoor coil combination.
2.After correct piston is installed, locate brass piston ring shipped in piston bag. Install piston ring behind metering piston as shown in Fig. 2. The piston ring will ensure piston stays seated during all operating conditions.
Step 5ÐMake Piping Connections
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
Outdoor units may be connected to indoor sections using accessory tubing package or
INSTALLATION RECOMMENDATIONS
1. Locate unit away from windows.
2.Ensure that vapor and liquid tube diameters are appropriate to capacity of unit. (See Table 1)
3.Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4.Leave some slack between structure and unit to absorb vibration.
5.When passing refrigerant tubes through wall, seal opening with RTV or other pliable
6.Avoid direct lineset contact with water pipes, ductwork, floor joists, wall studs, floors, and walls.
7.Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing. (See Fig. 3.)
NOTE: Avoid contact between tubing and structure
OUTDOOR WALL INDOOR WALL
CAULK
LIQUID TUBE
VAPOR TUBE
INSULATION
THROUGH THE WALL
| JOIST | |
HANGER STRAP |
| |
(AROUND VAPOR | INSULATION | |
TUBE ONLY) | ||
| ||
| VAPOR TUBE |
1″ MIN.
LIQUID TUBE
SUSPENSION
A94028
Fig. 3ÐPiping Installation
8.Ensure that tubing insulation is pliable and completely sur- rounds vapor line.
9.When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 3.)
10.Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT TUBING IN GROUND. If any section of tubing is buried, there must be a
2