38VYX050/38VYX080

Final installation checks

E N G L I S H

Piping cover Check points of outdoor unit Flare nut connections (Indoor unit) Valve cover

Check and Test Operation

For R410A, use the leak detector exclusively manufactured for HFC refrigerant (R410A, R134a, etc.).

The conventional leak detector for HCFC refrigerant (R22, etc.) cannot be used because its sensitivity for HFC refrigerant lowers to approx. 1/40.

Pressure of R410A is approx. 1.6 times higher than that of R22. If installation work is incompletely finished, a gas leakage may occur when pressure rises during operation.

Therefore, be sure to test the piping connections for leakage.

Check gas leakage at the flare nut connections, valve stem cap connections and service port cap fittings with a leak detector or soap water.

Useful Functions (38VYX080 only)

Self-Diagnosis by LED Indication

Troubles of the outdoor unit can be diagnosed by LED indications on the cycle control P.C. board of the outdoor unit. Utilize them for various checks.

For the check by remote controller of the indoor unit, refer to the Installation Manual of the outdoor unit.

Before a check, confirm each bit of the DIP switch is set to OFF position.

LED indication and code checking

LED indication

 

 

Cycle control

 

 

Cause

 

 

 

P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED indication

 

 

 

 

 

 

 

 

 

 

 

 

 

D800

 

D801

 

D802

 

D803

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger sensor (TE) error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction sensor (TS) error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot gas discharge sensor (TD) error

 

 

 

 

 

 

 

 

 

D800 O: Red

 

 

 

 

 

 

 

High-pressure protection error

D801 O: Yellow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor air temperature sensor error (TO)

D802 O: Yellow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor motorised fan error DC

 

 

 

 

 

 

 

 

 

D803 O: Yellow

 

 

 

 

 

 

 

Communication error between IPDU (Abnormal stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High-pressure release operation

 

 

 

 

 

 

 

 

 

: Flashing

 

 

 

 

 

 

 

Discharge temp. error: hot gas is too high

 

 

 

 

 

 

 

 

 

: Off

 

 

 

 

 

 

 

EEPROM error

 

 

 

 

 

 

 

 

 

: On

 

 

 

 

 

 

 

Communication error between IPDU (No abnormal stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G-Tr short-circuit protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detect circuit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current sensor error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Comp. lock error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Comp. break down

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GB - 11