Final installation checks
E N G L I S H
Piping cover Check points of outdoor unit Flare nut connections (Indoor unit) Valve cover
Check and Test Operation
For R410A, use the leak detector exclusively manufactured for HFC refrigerant (R410A, R134a, etc.).
•The conventional leak detector for HCFC refrigerant (R22, etc.) cannot be used because its sensitivity for HFC refrigerant lowers to approx. 1/40.
•Pressure of R410A is approx. 1.6 times higher than that of R22. If installation work is incompletely finished, a gas leakage may occur when pressure rises during operation.
Therefore, be sure to test the piping connections for leakage.
•Check gas leakage at the flare nut connections, valve stem cap connections and service port cap fittings with a leak detector or soap water.
Useful Functions (38VYX080 only)
Self-Diagnosis by LED Indication
Troubles of the outdoor unit can be diagnosed by LED indications on the cycle control P.C. board of the outdoor unit. Utilize them for various checks.
For the check by remote controller of the indoor unit, refer to the Installation Manual of the outdoor unit.
Before a check, confirm each bit of the DIP switch is set to OFF position.
LED indication and code checking
LED indication |
|
| Cycle control |
|
| Cause | ||
|
|
| P.C. board |
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
| LED indication |
|
|
| |||
|
|
|
|
|
|
|
|
|
| D800 |
| D801 |
| D802 |
| D803 |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Heat exchanger sensor (TE) error |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Suction sensor (TS) error |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Hot gas discharge sensor (TD) error |
|
|
|
|
|
|
|
|
|
D800 O: Red |
|
|
|
|
|
|
|
|
D801 O: Yellow |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Outdoor air temperature sensor error (TO) | |
D802 O: Yellow |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Outdoor motorised fan error DC | |
|
|
|
|
|
|
|
|
|
D803 O: Yellow |
|
|
|
|
|
|
| Communication error between IPDU (Abnormal stop) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
: Flashing |
|
|
|
|
|
|
| Discharge temp. error: hot gas is too high |
|
|
|
|
|
|
|
|
|
: Off |
|
|
|
|
|
|
| EEPROM error |
|
|
|
|
|
|
|
|
|
: On |
|
|
|
|
|
|
| Communication error between IPDU (No abnormal stop) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Detect circuit error |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Current sensor error |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Comp. lock error |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Comp. break down |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GB - 11