8

SYSTEM OPERATING ENVELOPE

53MVC/MVQ System Operating Envelope Chart
40
50
60
70
80
90
100
110
120
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Outdoor Temperature (ºF)
Indoor Temperature (ºF)
0
5
10
15
20
25
30
35
40
45
50
55
60
-40-35-30-25-20-15-10-5 0 5 1015202530354045505560
Outdoor Temperature (ºC)
Indoor Temperature (ºC)

Cooling

Continuous

Operation

Heating

Continuous

Operation

62ºF
55º
75ºF
55ºF
5ºF
80ºF
125º
Use low ambient control if the unit will operate in cooling at ambient conditions below 55_F (12.78_C).
A08180
Fig. 4 – System Operating Enevelope

ELECTRICAL DATA

UNIT
SIZE
OPERATING
VOLTAGE* COMPRESSOR OUTDOOR FAN INDOOR FAN MCA
MAX
FUSE/CB
AMP
MAX/MIN V O L T S --- P H --- H Z RLA LRA FLA HP WVOLTS FLA HP W
009 127/104 1 1 5 --- 1 --- 6 0 7.5 40 0.60 0.102 23 35 DC 1.1 0.034 20 12 20
012 9.9 47 1.18 0.044 25 15 25
012
253/187 208/230---1---60
5.2 21 0.38 0.116 36 35 DC 1.18 0.044 25 915
018 7.3 32.6 0.78 0.224 53 208/230---1---60 0.26 0.075 31 11 20
024 9.7 34.8 0.62 0.218 100 0.39 0.112 50 14 25
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND
FLA --- F u l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps

38/40MVC, MVQ