Electrical data

UNIT ELECTRICAL DATA

 

UNIT

 

 

VOLTAGE

COMPRESSOR

COMPRESSOR

 

 

V-PH-Hz

 

RANGE

 

NO. 1

 

NO. 2

 

50XCA

 

 

 

 

 

 

 

Min

 

Max

RLA

 

LRA

RLA

 

LRA

 

 

 

 

 

 

 

 

 

 

208/230-3-60

187

 

253

20.5

 

155

 

 

06

 

460-3-60

414

 

506

9.6

 

75

 

 

 

 

575-3-60

518

 

632

7.6

 

54

 

 

 

 

208/230-3-60

187

 

253

22.4

 

149

 

 

08

 

460-3-60

414

 

506

10.6

 

75

 

 

 

 

575-3-60

518

 

632

7.7

 

54

 

 

 

 

208/230-3-60

187

 

253

16.0

 

110

16.0

 

110

 

12

 

460-3-60

414

 

506

7.8

 

52

7.8

 

52

 

 

 

575-3-60

518

 

632

5.7

 

39

5.7

 

39

 

 

 

208/230-3-60

187

 

253

20.5

 

155

20.5

 

155

 

14

 

460-3-60

414

 

506

9.6

 

75

9.6

 

75

 

 

 

575-3-60

518

 

632

7.6

 

54

7.6

 

54

 

 

 

208/230-3-60

187

 

253

23.2

 

164

23.2

 

164

 

16

 

460-3-60

414

 

506

11.2

 

75

11.2

 

75

 

 

 

575-3-60

518

 

632

7.9

 

54

7.9

 

54

 

 

 

208/230-3-60

187

 

253

30.1

 

225

30.1

 

225

 

24

 

460-3-60

414

 

506

16.7

 

114

16.7

 

114

 

 

 

575-3-60

518

 

632

12.2

 

80

12.2

 

80

 

 

LEGEND

 

 

 

 

 

 

 

 

 

FLA

Full Load Amps

 

 

 

 

 

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

NEC

National Electrical Code

 

 

 

 

 

 

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

 

 

 

 

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR circuit breaker. Canadian units may be fuse or circuit breaker.

2.Wire sizing amps are a sum of 125% of the compressor RLA plus 100% of indoor fan motor FLA.

3.Motors are protected against primary single phasing condition.

4.Indoor-fan motors are 3-phase motors of same voltage as unit.

26

Page 26
Image 26
Carrier 50XCA06-24 manual Electrical data, Unit Electrical Data