Carrier 50XCA06-24 manual Performance data, Gross Cooling Capacities

Models: 50XCA06-24

1 36
Download 36 pages 45.61 Kb
Page 8
Image 8
Performance data

Performance data

GROSS COOLING CAPACITIES

50XCA06 (5 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering

 

 

 

 

 

AIR ENTERING EVAPORATOR — 80 F Edb (F) - CFM

 

 

 

 

 

 

 

2500

 

 

 

2000

 

 

 

1500

 

Condenser Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator — Ewb (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECT (F)

CFM

 

57

62

 

67

75

57

62

 

67

75

57

62

 

67

75

BF

0.20

0.10

 

0.10

0.03

0..34

0.15

 

0.14

0.10

0.44

0.22

 

0.18

0.15

 

 

 

 

 

 

 

TC

73.4

74.8

 

80.4

90.4

68.8

71.9

 

77.8

87.8

62.9

67.9

 

73.7

83.7

 

 

SHC

73.4

70.2

 

58.6

38.9

68.8

63.2

 

53.4

36.9

62.1

55.2

 

47.5

34.5

 

2100

LDB

53.08

54.40

 

58.75

65.92

48.48

51.18

 

55.83

63.36

42.07

46.49

 

51.34

59.30

 

 

LWB

45.41

51.41

 

56.79

65.43

43.16

48.97

 

54.36

63.10

39.61

45.04

 

50.43

59.29

 

 

kW

3.25

3.27

 

3.34

3.48

3.20

3.23

 

3.31

3.45

3.13

3.18

 

3.26

3.39

 

 

TC

74.0

75.7

 

81.5

92.2

69.3

72.7

 

78.8

89.4

63.3

68.5

 

74.5

85.0

55

2800

SHC

74.0

70.7

 

59.0

39.5

69.3

63.6

 

53.7

37.4

62.4

55.4

 

47.8

35.0

LDB

52.85

54.22

 

58.60

65.71

48.23

51.03

 

55.66

63.11

41.87

46.35

 

51.15

59.01

 

 

LWB

45.30

51.28

 

56.63

65.22

43.03

48.84

 

54.18

62.86

39.46

44.88

 

50.23

59.00

 

 

kW

2.85

2.86

 

2.90

2.98

2.82

2.84

 

2.88

2.96

2.79

2.82

 

2.85

2.93

 

 

TC

74.5

76.1

 

82.2

93.1

69.6

73.0

 

79.4

90.2

63.5

68.8

 

75.0

85.6

 

 

SHC

74.5

70.9

 

59.3

39.9

69.6

63.8

 

54.0

37.7

62.5

55.6

 

48.0

35.2

 

3500

LDB

52.70

54.13

 

58.49

65.59

48.09

50.95

 

55.54

62.97

41.79

46.23

 

51.01

58.88

 

 

LWB

45.22

51.21

 

56.54

65.11

42.96

48.76

 

54.08

62.73

39.39

44.77

 

50.11

58.87

 

 

kW

2.63

2.63

 

2.65

2.70

2.61

2.62

 

2.64

2.69

2.60

2.61

 

2.63

2.67

 

 

TC

68.7

69.3

 

74.4

83.5

64.6

66.7

 

72.1

81.3

59.0

63.2

 

68.6

77.8

 

 

SHC

68.7

67.3

 

56.1

36.5

64.6

60.6

 

50.9

34.5

59.0

52.8

 

45.1

32.2

 

2100

LDB

54.80

55.46

 

59.67

66.79

50.37

52.37

 

56.96

64.42

43.96

47.94

 

52.76

60.63

 

 

LWB

46.22

52.26

 

57.64

66.23

44.09

50.05

 

55.40

64.09

40.86

46.40

 

51.77

60.58

 

 

kW

4.29

4.29

 

4.37

4.52

4.23

4.26

 

4.34

4.48

4.15

4.21

 

4.28

4.43

 

 

TC

69.5

70.3

 

75.5

85.2

65.2

67.6

 

73.1

82.8

59.5

63.8

 

69.5

79.1

 

 

SHC

69.5

67.8

 

56.5

37.1

65.2

61.1

 

51.3

35.0

59.5

53.1

 

45.5

32.7

75

2800

LDB

54.52

55.26

 

59.51

66.59

50.10

52.17

 

56.76

64.18

43.66

47.76

 

52.54

60.36

 

 

LWB

46.09

52.11

 

57.48

66.04

43.96

49.87

 

55.21

63.86

40.70

46.22

 

51.55

60.31

 

 

kW

3.83

3.84

 

3.88

3.96

3.80

3.82

 

3.86

3.94

3.76

3.79

 

3.83

3.91

 

 

TC

70.0

70.9

 

76.3

86.2

65.6

68.0

 

73.8

83.8

59.7

64.2

 

70.0

79.8

 

 

SHC

70.0

68.1

 

56.8

37.5

65.6

61.3

 

51.6

35.4

59.7

53.3

 

45.7

33.0

 

3500

LDB

54.34

55.15

 

59.39

66.45

49.93

52.09

 

56.63

64.03

43.50

47.63

 

52.39

60.18

 

 

LWB

46.01

52.03

 

57.37

65.92

43.87

49.79

 

55.10

63.72

40.62

46.10

 

51.42

60.14

 

 

kW

3.57

3.58

 

3.60

3.64

3.56

3.56

 

3.59

3.63

3.54

3.55

 

3.57

3.61

 

 

TC

63.4

63.5

 

67.6

75.8

59.8

60.9

 

65.7

74.0

54.9

57.8

 

62.8

71.1

 

 

SHC

63.4

63.5

 

53.3

33.9

59.8

57.7

 

48.2

31.9

54.9

50.2

 

42.5

29.7

 

2100

LDB

56.74

56.84

 

60.66

67.73

52.58

53.68

 

58.16

65.57

46.46

49.52

 

54.32

62.13

 

 

LWB

47.14

53.16

 

58.57

67.11

45.16

51.21

 

56.55

65.18

42.14

47.93

 

53.26

62.00

 

 

kW

5.48

5.48

 

5.55

5.70

5.42

5.43

 

5.52

5.67

5.28

5.38

 

5.47

5.62

 

 

TC

64.3

64.5

 

68.8

77.5

60.5

61.9

 

66.8

75.5

55.3

58.5

 

63.7

72.4

 

 

SHC

64.3

64.5

 

53.7

34.4

60.5

58.1

 

48.6

32.4

55.3

50.4

 

42.9

30.2

95

2800

LDB

56.44

56.48

 

60.53

67.54

52.26

53.49

 

57.99

65.34

46.21

49.36

 

54.11

61.85

 

 

LWB

46.99

53.01

 

58.41

66.92

45.01

51.02

 

56.36

64.96

42.01

47.73

 

53.03

61.73

 

 

kW

4.99

4.99

 

5.03

5.11

4.95

4.97

 

5.01

5.09

4.91

4.94

 

4.98

5.06

 

 

TC

64.8

65.0

 

69.6

78.6

61.0

62.4

 

67.5

76.5

55.7

59.0

 

64.3

73.3

 

 

SHC

64.8

65.0

 

54.1

34.8

61.0

58.4

 

48.9

32.8

55.7

50.7

 

43.2

30.5

 

3500

LDB

56.23

56.29

 

60.39

67.40

52.05

53.36

 

57.84

65.18

45.99

49.20

 

53.93

61.66

 

 

LWB

46.90

52.93

 

58.30

66.80

44.91

50.91

 

56.23

64.81

41.90

47.59

 

52.88

61.55

 

 

kW

4.70

4.71

 

4.73

4.77

4.69

4.70

 

4.72

4.76

4.66

4.68

 

4.70

4.75

 

 

TC

60.4

60.5

 

63.8

71.6

57.1

57.7

 

62.2

70.0

52.4

54.8

 

59.5

67.4

 

 

SHC

60.4

60.5

 

51.8

32.5

57.1

56.0

 

46.7

30.5

52.4

48.7

 

41.1

28.3

 

2100

LDB

57.84

57.93

 

61.22

68.24

53.82

54.46

 

58.84

66.20

47.96

50.43

 

55.18

62.95

 

 

LWB

47.64

53.62

 

59.08

67.59

45.76

51.83

 

57.17

65.77

42.90

48.76

 

54.07

62.78

 

 

kW

6.11

6.11

 

6.17

6.32

6.05

6.06

 

6.14

6.29

5.96

6.01

 

6.10

6.24

 

 

TC

61.3

61.4

 

65.0

73.3

57.8

58.7

 

63.2

71.5

53.0

55.6

 

60.4

68.7

105

 

SHC

61.3

61.4

 

52.1

33.0

57.8

56.5

 

47.1

31.0

53.0

49.1

 

41.4

28.8

2800

LDB

57.52

57.61

 

61.09

68.06

53.49

54.26

 

58.67

65.98

47.63

50.19

 

54.97

62.67

 

 

LWB

47.50

53.48

 

58.92

67.40

45.61

51.63

 

56.99

65.55

42.73

48.52

 

53.85

62.51

 

 

kW

5.62

5.62

 

5.66

5.75

5.59

5.60

 

5.64

5.73

5.54

5.57

 

5.62

5.70

 

 

TC

61.9

62.0

 

65.9

74.4

58.3

59.3

 

64.0

72.6

53.4

56.0

 

61.1

69.6

 

 

SHC

61.9

62.0

 

52.5

33.4

58.3

56.8

 

47.4

31.4

53.4

49.3

 

41.8

29.2

 

3500

LDB

57.29

57.39

 

60.94

67.91

53.26

54.11

 

58.50

65.80

47.38

50.08

 

54.78

62.46

 

 

LWB

47.39

53.39

 

58.80

67.27

45.49

51.53

 

56.85

65.40

42.61

48.42

 

53.68

62.32

 

 

kW

5.34

5.34

 

5.36

5.41

5.32

5.33

 

5.35

5.40

5.29

5.31

 

5.33

5.38

 

 

TC

57.3

57.3

 

59.9

67.3

54.2

54.3

 

58.4

65.8

49.9

51.5

 

56.1

63.6

 

 

SHC

57.3

57.3

 

50.2

31.0

54.2

54.3

 

45.1

29.1

49.9

47.1

 

39.6

27.0

 

2100

LDB

59.00

59.09

 

61.79

68.77

55.15

55.22

 

59.53

66.84

49.53

51.38

 

56.07

63.77

 

 

LWB

48.18

54.09

 

59.60

68.07

46.39

52.48

 

57.82

66.37

43.68

49.64

 

54.92

63.57

 

 

kW

6.76

6.76

 

6.81

6.95

6.70

6.70

 

6.78

6.93

6.61

6.64

 

6.74

6.88

 

 

TC

58.3

58.3

 

61.2

68.9

55.1

55.4

 

59.6

67.4

50.6

52.4

 

57.1

64.9

115

 

SHC

58.3

58.3

 

50.7

31.6

55.1

54.5

 

45.6

29.6

50.6

47.5

 

40.0

27.4

2800

LDB

58.63

58.72

 

61.62

68.58

54.76

55.16

 

59.33

66.61

49.11

51.15

 

55.82

63.49

 

 

LWB

48.01

53.94

 

59.43

67.89

46.21

52.28

 

57.62

66.15

43.47

49.40

 

54.67

63.29

 

 

kW

6.28

6.28

 

6.32

6.40

6.25

6.25

 

6.30

6.38

6.19

6.22

 

6.27

6.36

 

 

TC

58.8

58.8

 

62.0

69.9

55.5

55.9

 

60.2

68.3

50.9

52.8

 

57.6

65.7

 

 

SHC

58.8

58.8

 

51.0

31.9

55.5

54.9

 

45.9

29.9

50.9

47.7

 

40.2

27.7

 

3500

LDB

58.45

58.54

 

61.49

68.46

54.58

54.99

 

59.21

66.47

48.92

51.03

 

55.69

63.32

 

 

LWB

47.92

53.87

 

59.32

67.78

46.12

52.17

 

57.51

66.02

43.38

49.29

 

54.54

63.14

 

 

kW

6.00

6.00

 

6.02

6.06

5.99

5.99

 

6.01

6.06

5.95

5.97

 

6.00

6.04

 

 

 

LEGEND

 

 

BF

Bypass Factor

EWB — Entering Wet Bulb (F)

SHC

Sensible Capacity (1000 Btu/hr)

ECT

Entering Condenser Temperature (F)

LDB — Leaving Dry Bulb (F)

TC

Total Capacity (1000 Btu/hr)

EDB —

Entering Dry Bulb (F)

LWB — Leaving Wet Bulb (F)

kW

Compressor Motor Power Input (kilowatts)

8

Page 8
Image 8
Carrier 50XCA06-24 manual Performance data, Gross Cooling Capacities