PHYSICAL DATA

PHYSICAL DATA

Physical Data-Unit 50XP

UNIT SIZE

024

030

 

036

 

 

042

048

 

060

NOMINAL CAPACITY (ton)

2

2---1/2

 

3

 

 

3---1/2

4

 

5

SHIPPING WEIGHT (lb)

356

360

 

378

 

 

436

470

 

515

SHIPPING WEIGHT (kg)

161

163

 

171

 

 

198

213

 

234

 

 

 

 

 

 

 

 

 

 

 

COMPRESSORS

 

 

 

 

Scroll

 

 

 

Quantity

 

 

 

 

1

 

 

 

REFRIGERANT (R---410A)

7.3

8.0

 

9.5

 

 

10.7

11.25

 

13.2

Quantity (lb.)

 

 

 

 

Quantity (kg)

3.3

3.6

 

4.3

 

 

4.9

5.1

 

6.0

REFRIGERANT METERING DEVICE

 

 

 

 

TXV

 

 

 

OUTDOOR COIL

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

2...21

2...21

 

2...21

 

 

2...21

2...21

 

2...21

Face Area (sq ft)

11.95

12.0

 

13.6

 

 

15.4

17.4

 

19.3

OUTDOOR FAN

 

 

 

 

 

 

 

 

 

 

Nominal Cfm

2350

2700

 

2350

 

 

2800

3300

 

3300

Diameter (in.)

22

22

 

22

 

 

22

22

 

22

Diameter (mm)

558.8

558.8

 

558.8

 

 

558.8

558.8

 

558.8

Motor Hp (Rpm)

1/8 (825)

1/8 (825)

 

1/8 (825)

 

 

1/8 (825)

1/4 (1100)

 

1/4 (1100)

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

3...15

3...15

 

4...15

 

 

3...15

4...15

 

4...17

Face Area (sq ft)

3.7

3.7

 

3.7

 

 

4.7

4.7

 

5.7

 

 

 

 

 

 

 

 

 

 

 

INDOOR BLOWER

 

 

 

 

 

 

 

1400

 

1750

Nominal Cooling Airflow (Cfm)

800

1000

 

1100

 

 

1400

 

 

 

 

11x10

 

11x10

Size (in.)

10x10

10x10

11x10

 

 

11x10

 

Size (mm.)

254x254

254x254

279.4x254

 

 

279.4x254

279.4x254

 

279.4x254

Motor HP (RPM)

1/2 (1050)

1/2 (1050)

 

3/4 (1000)

 

 

3/4 (1075)

3/4 (1075)

 

1.0 (1040)

 

 

 

 

 

 

 

 

 

 

HIGH ---PRESSURE SWITCH

 

 

 

650

 

+/ --- 15

 

 

 

(psig) Cut---out Reset (Auto)

 

 

 

420 +/ --- 25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOSS---OF---CHARGE / LOW---PRESSURE

 

 

 

20 +/ --- 5

 

 

 

SWITCH (Liquid Line) (psig) cut---out Re-

 

 

 

 

 

 

 

 

 

45 +/ --- 10

 

 

 

set (auto)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN---AIR FILTERS†}

20x20x1

 

20x24x1

 

 

 

24x30x1

 

 

Throwaway Size (in.)

 

 

 

 

 

 

Throwaway Size (mm)

508x508x25

 

508x610x25

 

 

 

610x762x25

 

 

 

 

 

 

 

 

 

 

 

 

 

{Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C..

}If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.