TEST/TWIN

COM W Y R G 24V

HUM

24-V THERMOSTAT TERMINALS

HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX)

LED OPERATION & DIAGNOSTIC LIGHT

 

HARNESS CONNECTOR

SEC-1

24-V TRANSFORMER SEC-2

 

3-AMP FUSE

SPARE-1

COOL

BLOWER SPEED

HEAT

 

SELECTION TERMINALS

 

SPARE-2

 

EAC-1

 

EAC-ELECTRONIC AIR CLEANER

 

TERMINALS (115-VAC 1.5 AMP MAX)

115-VAC (L1)

EAC-2

POWER SUPPLY

115-VAC (L2) NEUTRAL

 

 

CONNECTION

HOT SURFACE

INDUCER MOTOR

IGNITOR CONNECTOR

CONNECTOR

A95086

Fig. 12ÐControl Center

4.BRIEFLY remove either wire from the main limit switch until the LED goes out, then reconnect it.

Make sure limit switch wire does not contact any metallic component such as the gas valve. If wire is shorted, 3-amp fuse on control center will blow.

NOTE: If wire to main limit is disconnected longer than 4 sec, the control senses limit circuit is open. Main blower will start and retrieval request will be ignored.

5.When above items have been completed, the component test sequence will occur as described in the Component Test Sequence section above.

NOTE: Be sure to record the fault code which is flashed 4 times at start of component test for further troubleshooting.

6.After component test is completed and LED is ON continu- ously indicating the furnace is ready to operate when a signal from the thermostat is received, replace main furnace door.

INITIATING COMPONENT TEST AND RETRIEVING STA- TUS CODE BY JUMPERING CONTROL TEST TERMINAL

1.Remove main furnace door.

2.Remove blower access panel.

3.Manually close blower access panel door switch. Use a piece of tape to hold switch closed.

Blower access panel door switch opens 115-v power to control center. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warning could result in electrical shock, personal injury, or death.

4.BRIEFLY short (jumper) TEST, 1/4-in. quick-connect termi- nal on control center (adjacent to the LED diagnostic light) and the COM terminal on thermostat connection block. (See Fig. 12.)

NOTE: If TEST to COM terminals are jumpered longer than 2 sec, LED will flash rapidly, and retrieval request will be ignored.

5.When above items have been completed, the component test sequence will occur as described in the Component Test Sequence section above.

NOTE: Be sure to record the fault code which is flashed 4 times at start of component test for further troubleshooting.

6.After component test is completed and furnace is operating properly, release blower access panel door switch, replace blower access panel, and replace main furnace door.

Step 9ÐChecking Heat Tape Operation (If Applicable)

In applications where the ambient temperature around the furnace is 32°F or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it will operate when low temperatures are present.

NOTE: Heat tape, when used, should be wrapped around the condensate drain trap and drain line. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Check the following:

9

Page 9
Image 9
Carrier 58MSA instruction manual ÐControl Center, ÐChecking Heat Tape Operation If Applicable