Carrier ASPAS1CCA007 Specifications, 1.6SYSTEM SET LED, 1.7FUEL REQUIREMENTS AND RECOMMENDATIONS

Models: ASPAS1CCA007

1 24
Download 24 pages 6.05 Kb
Page 8
Image 8
SPECIFICATIONS

Section 1 — General Information

Carrier Air-cooled 7 kW, 12 kW and 15 kW Generators

1.5

SPECIFICATIONS

 

 

 

 

‹ 1.5.1 GENERATOR

 

 

 

 

Model

 

ASPAS1CCA007

 

ASPAS1CCA012

ASPAS1CCA015

Rated Max. Continuous Power Capacity (Watts*)

6,000 NG/7,000 LP

 

12,000 NG/12,000 LP

13,000 NG/15,000 LP

Rated Voltage

120/240

 

120/240

120/240

Rated Max. Continuous Load Current (Amps)

 

 

 

 

 

120 Volts**

50.0 NG/58.3 LP

 

100.0 NG/100.0 LP

108.3 NG/125.0 LP

 

240 Volts

25.0 NG/29.2 LP

 

50.0 NG/50.0 LP

54.2 NG/62.5 LP

Main Line Circuit Breaker

30 Amp

 

50 Amp

65 Amp

Phase

 

1

 

1

1

Number of Rotor Poles

2

 

2

2

Rated AC Frequency

60 Hz

 

60 Hz

60 Hz

Power Factor

1

 

1

1

Recommended Air Filter

Carrier Part # 0C8127

 

Carrier Part # 0C8127

Carrier Part # 0C8127

Battery Requirement

Group 26

 

Group 26

Group 26

(At 0° F -17.8°C)

12 Volts and

 

12 Volts and

12 Volts and

 

 

 

350 Cold-cranking

 

525 Cold-cranking

525 Cold-cranking

 

 

 

Amperes Minimum

 

Amperes Minimum

Amperes Minimum

Weight

 

375 Pounds

 

470 Pounds

487 Pounds

Output Sound Level @ 23 ft (7m) at full load

68 db (A)

 

70.5 db (A)

71.5 db (A)

Normal Operating Range

 

-20°F (-28.8°C) to 104°F (40°C)

*Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60° F) ambient temperature.

**Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value stated for 240 volts.

‹1.5.2 ENGINE

 

 

ASPAS1CCA007

ASPAS1CCA012

ASPAS1CCA015

 

 

Type of Engine

GH-410

GT-990

GT-990

 

 

Number of Cylinders

1

2

2

 

 

Rated Horsepower

14.5 @ 3,600 rpm

30 @ 3,600 rpm

30 @ 3,600 rpm

 

 

Displacement

410cc

992cc

992cc

 

 

Cylinder Block

Aluminum w/Cast

Aluminum w/Cast

Aluminum w/Cast

 

 

 

Iron Sleeve

Iron Sleeve

Iron Sleeve

 

 

Valve Arrangement

Overhead Valves

Overhead Valves

Overhead Valves

 

 

Ignition System

Solid-state w/Magneto

Solid-state w/Magneto

Solid-state w/Magneto

 

 

Recommended Spark Plug

RC14YC

RC12YC

RC12YC

 

 

Spark Plug Gap

0.76 mm (0.030 inch)

0.508 mm (0.020 inch)

0.508 mm (0.020 inch)

 

 

Compression Ratio

8.6:1

9.5:1

9.5:1

 

 

Starter

12 Vdc

12 Vdc

12Vdc

 

 

Oil Capacity Including Filter

Approx. 1.5 Qts

Approx. 1.7 Qts

Approx. 1.7 Qts

 

 

Recommended Oil Filter

Carrier Part # 70185D

Carrier Part # 70185D

Carrier Part # 70185D

 

 

Recommended Air Filter

Carrier Part # 0C8127

Carrier Part # 0C8127

Carrier Part # 0C8127

 

 

Operating RPM

3,600

3,600

3,600

 

 

 

 

 

 

 

1.6SYSTEM SET LED

The “System Set” LED is lit when all of the following conditions are true:

1.The AUTO/OFF/MANUAL switch is set to the AUTO position.

2.The utility voltage being supplied to the unit is being sensed by the PCB. If the utility sense voltage is not connected to the unit or if it is below 168 volts AC, then the system set light will flash rapidly. This indicates that if the AUTO/OFF/ MANUAL switch is placed in the Auto position, the generator will start.

3.The “Not In Auto” dip switch is set to the OFF position on the control board.

4.No alarms are present, for example, low oil pressure, high temperature, etc.

1.7FUEL REQUIREMENTS

AND RECOMMENDATIONS

With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank. The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas.

6 Carrier

Page 8
Image 8
Carrier ASPAS1CCA007 Specifications, 1.6SYSTEM SET LED, 1.7FUEL REQUIREMENTS AND RECOMMENDATIONS, ‹ 1.5.1 GENERATOR