6.If you are using an extension cord outdoors, make sure it is marked with the suffix “W-A” (“W” in Canada) to indicate it is acceptable for outdoor use.

7.Make sure the extension cord is prop- erly wired and in good electrical con- dition. Always replace a damaged extension cord or have it repaired by a qualified electrician before using it.

8.Protect the extension cords from sharp objects, excessive heat, and damp or wet areas.

RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*

(120/240 VOLT)

NAMEPLATE

EXTENSION CORD

 

LENGTH

 

AMPERES

 

 

25’

50’

75’

100’

150’

(at full load)

 

 

 

 

 

 

 

 

 

 

 

0 – 2.0

18

18

18

18

16

2.1

– 3.4

18

18

18

16

14

3.5

– 5.0

18

18

16

14

12

5.1

– 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1

– 16.0

14

12

10

-

-

16.1

– 20.0

12

10

-

-

-

TABLE A

* Based on limiting the line

voltage drop to five volts at

150% of the rated amperes.

Symbology

Double Insulated

 

Canadian Standards Association

 

 

 

Underwriters Laboratories, Inc.

 

 

V~

Volts Alternating Current

A

Amperes

 

 

 

n0 xxxx/min.

No Load Revolutions per Minute

(RPM)

SKU 93749

For technical questions, please call 1-800-444-3353.

Page 6

Page 6
Image 6
Chicago Electric 93749 operating instructions Symbology, 25’ 50’ 75’