Installation Instructions
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 4 |
|
|
| WT |
|
|
|
| |||||||
|
|
|
| |||||||
|
|
|
|
|
| (Supersedes PK477) | PK477 |
161-506096-001
JUNE, 1995
Type WT Room Thermostat
2.86"
(73)
2.14"
(54)
4.72"
(110)
Front View | Side View |
Specifications — Table A
| Temp |
|
| Maximum Rating |
| ||
Model | Range | Contacts |
|
|
|
|
|
(°F) |
| 128V AC | 208V AC | 240V AC | 277V AC | Pilot Duty | |
|
| ||||||
|
|
|
|
|
|
| 125V AC |
SPST | 22 amps | 22 amps | 22 amps | 18 amps | (use with | ||
|
|
| or 2640 | or 4575 | or 5280 | or 5000 | AC |
DPST | total watts | total watts | total watts | total watts | contactor) | ||
|
|
|
|
|
|
|
|
GENERAL
Note: Type WT thermostats are designed for temperature control service only. Because they do not fail safe, they should not be used for temperature limiting duty.
WARNING: Users should install adequate
WARNING: Not for use in hazardous environments as described in the National Electrical Code. Failure to comply can result in explosion or fire.
Thermostat Location
1.Mount in any standard electrical outlet box. Use of extra deep box (3” x 2” x 31/2”) makes for easier wiring.
2.Locate outlet box about 5’ above floor on inside wall.
3.Box location should be representative of the area to be con- trolled. Avoid locations that are subject to drafts or false exter- nal heat (such as solar radiation, direct heat from heaters, etc.). Insure that the wall selected is capped to prevent drafts within the wall.