Limited Warranty:

14.STANDARD HEAT TRANSFER SYSTEM TROUBLE SHOOTING CHART

 

Problem

Cause

Corrective Action

 

 

System temperature too high for oil

See fluid manufacturer’s data for

 

 

causing vapor lock

maximum oil temperature

 

 

 

 

 

 

Vapors lock due to steam or air in oil

Bleed air & steam from system, change

 

Insufficient suction pressure (0 or

 

oil if problem continues

J

vacuum), pump noisy, gauges

 

 

Net positive suction pressure too low

Raise expansion tank to increase suction

 

vibrating, discharge pressure low

 

head, static head should be 4-5 psig.

 

(below 20 psig)

 

 

 

(See expansion tank location No. 6)

 

 

 

 

 

 

 

 

 

Strainer plugged

Remove and clean strainer

 

 

 

 

 

 

Valve closed

Check all valves

 

 

 

 

 

High discharge pressure over 40 psig,

System piping blocked or restricted

Check all valves, check strainer

 

 

 

K

pressure gauges fluctuating rapidly,

 

Check process piping sizing, check for

pump noisy, expansion tank normal,

Process piping blocked or restricted

closed valves or improperly installed

 

system operating on bypass relief

automatic valves, check all bleed

 

 

 

valve

 

valves for air or steam

 

 

Steam or water in oil

Bleed system, change oil

 

 

 

 

 

 

Expansion tank too low

Expansion tank should be mounted 15 ft.

L

Expansion tank overflows or “burps”

 

above system

(over 220°F)

 

 

Expansion tank line too short

Lengthen expansion tank line to cool oil

 

 

 

 

 

and provide cold oil seal

 

 

 

 

 

 

Tank too small for system

Check volume on process piping

 

 

 

 

 

 

Over-temperature control open

Set thermostat above process temperature

M

Control relay #1 will not close

 

and reset

 

 

Pressure switch not closed

See N

 

 

Switch set wrong

Set pressure switch to approximately 5 psi

 

 

 

over suction gauge pressure

 

 

 

 

N

 

 

Check pump & motor rotation, see arrow

Pressure switch will not close

Pump running backwards

on motor, reverse phase lead on circuit

 

 

 

breaker

 

 

 

 

 

 

Not enough or no fluid in system

Check fluid levels in expansion tank,

 

 

 

make sure all valves are open

 

 

 

 

 

 

Pump cavitating

See O

 

 

 

 

 

 

 

Bleed system periodically until all air or

 

 

Air or steam in system

stem is removed

 

 

Insufficient bleed valves in process

O

 

 

Pump noisy and/or cavitation

 

piping to remove trapped air

 

 

 

 

 

 

Contaminated oil

Change oil

 

 

 

 

 

 

Pump damaged by overtightened

 

 

 

packing gland

Replace pump

 

 

 

 

 

 

Insufficient suction pressure

Suction pressure should be 4-5 psig

 

 

 

 

Limited Warranty:

Please refer to the Chromalox limited warranty applicable to this product at

http://www.chromalox.com/customer-service/policies/termsofsale.aspx.

2150 N. RULON WHITE BLVD., OGDEN, UT 84404

Phone: 1-800-368-2493

www.chromalox.com

Page 6
Image 6
Chromalox PQ410-4 service manual Limited Warranty, Problem, Cause, Corrective Action