FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor- mance” table listed above represents blower performance WITHOUT filters.

All applications of these furnaces require the use of field installed air filters. All filter media and mounting hardware or provisions must be field installed external to the furnace cabi- net. DO NOT attempt to install any filters inside the furnace.

NOTE: Single side return above 1800 CFM is approved as long as the filter velocity does not exceed filter manufac- turer’s recommendation and a transition is used to allow use on a 20x25 filter.

Recommended Filter Sizes (High velocity 600 FPM)

CFM

Cabinet

Side

Bottom

Size

(in)

(in)

 

800

A

16 x 25

14 x 25

1000

A

16 x 25

14 x 25

1200

A

16 x 25

14 x 25

1200

B

16 x 25

16 x 25

 

 

 

 

1600

B

16 x 25

16 x 25

1600

C

16 x 25

20 x 25

2000

C

(2) 16 x 25

20 x 25

2200

C

(2) 16 x 25

20 x 25

2000

D

(2) 16 x 25

22 x 25

NOTES:

1.Air velocity through throwaway type filters may not exceed 300 feet per minute (91.4 m/min). All velocities over this require the use of high velocity filters.

2.Do not exceed 1800 CFM using a single side return and a 16x25 filter. For CFM greater than 1800, you may use two side returns or one side and the bottom or one return with a transition to allow use of a 20x25 filter.

Unit Clearances to Combustibles

Application

Upflow

Downflow

Horizontal

Top

1"

0"

0"

Vent

0"

0"

0"

Rear

0"

0"

0"

Side

0"

0"

1"

Front*

0"

0"

0"

Floor

Combustible

Combustible1

Combustible

Closet

Yes

Yes

Yes

Line Contact

No

No

Yes

1. For combustible floors only when used with special sub-base.

*- 24" clearance in front and 18" on side recommended for service access. All furnaces approved for alcove and attic installation.

ACCESSORIES

PROPANE (LP) CONVERSION KIT -

S1-1NP0347 - All Models except 130K Model

S1-1NP0501 - 130K Model

This accessory conversion kit may be used to convert natural gas (N) units for propane (LP) operation.

CONCENTRIC VENT TERMINATION -

S1-1CT0302 (2")

S1-1CT0303 (3")

For use through rooftop, sidewall. Allows combustion air to enter and exhaust to exit through single common hole. Elimi- nates unslightly elbows for a cleaner installation.

Johnson Controls Unitary Products

400992-CTG-B-0708

SIDEWALL VENT TERMINATION KIT -

S1-1HT0901 (3")

S1-1HT0902 (2")

For use on sidewall, two-pipe installations only. Provide a more attractive termination for locations where the terminal is visable on the side of the home.

CONDENSATE NEUTRALIZER KIT - 1NK0301

Neutralizer cartridge has a 1/2" plastic tube fittings for instal- lation in the drain line. Calcium carbonate refill media is also available from the Source 1 Parts (p/n 026-30228-000).

SIDE RETURN FILTER RACKS -

S1-1SR0200 - All Models

S1-1SR0402 - All Models

S1-1SF0101 - All Models (Upflow Only)

BOTTOM RETURN FILTER RACKS -

S1-1BR0514 or 1BR0614 - For 14-1/2” cabinets S1-1BR0517 or 1BR0617 - For 17-1/2” cabinets S1-1BR0521 or 1BR0621 - For 21” cabinets

S1-1BR0524 or 1BR0624 - For 24-1/2” cabinets

1BR05xx series are galvanized steel filter racks. 1BR06xx are pre-painted steel filter racks to match the appearance of the furnace cabinet.

COMBUSTIBLE FLOOR BASE KIT -

For installation of these furnaces in downflow applications directly onto combustible flooring material, These kits are required to prevent potential overheating situations.tible floor base kit provides access for combustible airflow.

S1-1CB0514 - For 14-1/2” cabinets

S1-1CB0517 - For 17-1/2” cabinets

S1-1CB0521 - For 21” cabinets

S1-1CB0524 - For 24-1/2” cabinets

EAC TRANSITION KITS -

For installation of EAC accessories with these furnaces to provide easy transition of return airflow through the EAC to get the proper sealing and reduced airflow leakage.

S1-1TK1001 - For all models using side return

S1-1TK1014 - For 14-1/2” cabinets using bottom return S1-1TK1017 - For 17-1/2” cabinets using bottom return S1-1TK1021 - For 21” cabinets using bottom return

S1-1TK1024 - For 24-1/2” cabinets using bottom return

HIGH ALTITUDE PRESSURE SWITCHES -

For installation where the altitude is less than 5,000 feet it is not required that the pressure switch be changed. For alti- tudes above 5,000 feet, see kits below.

S1-1PS3306 - 040, 080

S1-1PS3307 - 060

S1-1PS3302 - 100, 120, 130

ROOM THERMOSTATS - A wide selection of compatible thermosets are available to provide optimum performance and features for any installation.

1H/1C, manual change-over electronic non-programmable thermostat.

1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.

1H/1C, auto/manual changeover, electronic programmable.

*For the most current accessory information, refer to the price book or consult factory.