3-8 Compaq 2000 Series UPS Operation and Reference Guide
Overcurrent Protection
Overcurrent protection is provided using t he resettable circuit breakers located
on the rear panel. The following models ha ve overcurrent protection:
Table 3-7
Overcurrent Protection
UPS Model Device
T2000 Circuit breakers for each load segment
T2000j Circuit breakers for each load segment
T2400h Input circuit breaker
No protection for load segments
T2400h-NA Input circuit breaker
No protection for load segments
Placing the UPS in Operate ModeThe 2000 Series UPS may be placed in Operate mode if either of the following
conditions apply:
■ The UPS is powered up and in Standby mode (LED 16 is off )
■ The UPS is powered off; no utility power is availa ble
Press and hold the ON button ( ) until the LED 16 (ON LED ) turns green,
indicating that power is available at the UPS output receptacles. The UPS
acknowledges compliance with a short beep.
IMPORTANT: If using battery power (no utility power present), press the ON button and
hold for three seconds. The UPS will conserve battery power by omitting the self-test.