2-8 AlphaServer GS80/160/320 Site Preparation

Table 2–6 Power Specifications of a GS160 with Two System Boxes
Specification U.S./Canada/Japan Europe
Voltage,Vrms 1120/208 or 202 380–415
Frequency, Hz 50–60 50–60
Phases 2circuits
3-phase star or
3-wire+N+GND
2circuits
3-phase delta
3-wirejunct. GND
or4-wire-mid-GND
2circuits
3-phase star
3-wire+N+GND
Power plug, quantity L21-30P,2 IEC3095P 32A , 2
Maximuminput
current/phase
21A 13A
Rating 30A 32A
Surge current 170A peak 170A peak
TotalVA 26,800 6,800
Totalpower 26,700watts 6,700watt s
Heat output 222,900 Btu/hr 22,900 Btu/hr
Powercord length 15ft/4.5 m 15ft/4.5m
Power cap (system) 2 DEC 12-12314-00 2DEC 12-14379-06
Receptacle (site)
(industry equiv.)
2DEC 12-12315-01
2NEMA L21-30R
2Hubbell 532R 6W
2IEC 309 (32A )
1TheUS/C anada/Japanmode lsuppo rts at hree-phase star connected source with nominal voltage of
115-127V/200-220V or a three-phase delta c onnected source wit h a nominal voltage of 200-240V.
TheE urope model supports a three-phase star c onnected source with a nominal voltage of 200-
240V/346-415V.
2Based on fully loaded system with two PCI boxes and one storage shelf in the powe r cabinet.