QuickSpecs
ProLiant BL20p and
Technical Specifications
Operating and Performance Specifications for Power Distribution Devices
| Power Bus Box | Mini Bus Bar | Scalable Bus Bar |
Power enclosures or facility | 1 | 1 | 2 |
DC feeds supported |
|
|
|
(3U each) |
|
|
|
|
|
|
|
Server blade enclosures | 1 | 3 | 5 |
supported (6U each) |
|
|
|
|
|
|
|
Total rack height of supported | 9U | 21U | 36U |
enclosures |
|
|
|
|
|
|
|
Dimensions |
|
|
|
Height | 5.1 in/12.95 cm | 19.45 in/49.40 cm | 48.57 in/123.37 cm |
Width | 3.6 in/9.14 cm each | 19.74 in/50.14 cm | 19.74 in/50.14 cm |
Depth | 3.25 in/8.26 cm | 2.2 in/5.59 cm | 2.2 in/5.59 cm |
|
|
|
|
Weight | 3.62 lb/1.64 kg | 13.2 lb/59.9 kg | 26 lb/11.79 kg |
|
|
|
|
Rated operating voltage | |||
|
|
|
|
Max total power supported | 3000 W | 9000 W | 15,000 W |
|
|
|
|
Total max input current at | 69.44 A at | 208.32 A at | 347.2 A at |
minimum voltage |
|
| (equivalent of 175A per |
|
|
| feed) |
|
|
|
|
Total max input current at | 62.5 A at | 187.5 A at | 312.5 A at |
nominal voltage |
|
| (equivalent of 175A per |
|
|
| feed) |
|
|
|
|
Max current per power feed | 70A | 210A | 210A |
|
|
|
|
Max local ambient | 149° F/65° C | 149° F/65° C | 149° F/65° C |
temperature |
|
|
|
Note: All systems support redundant A & B feeds. Scalable bus bar supports dual A and dual B feeds.
Canada — Version 1 — August 26, 2002 | 21 |