Notification
POWERPATH™ NAC POWER SUPPLIES
Description
The Wheelock Series
The Power Supplies may be connected to any 12V or 24V (FWR or DC) Fire Alarm Control Panel (FACP) by using a Notification Appliance Circuit (NAC) or a “Dry Contact”. Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support system accessories. This unit provides filtered and regulated 24VDC, up to four (4) Class “B”, two (2) Class “A”, or two (2) Class “B” and one (1) Class “A” Notification Appliance Circuits. With the optional
(4)Class “A” Notification Appliance Circuits. Additionally, an auxiliary power output of 2.5 Amps (disconnected upon AC power loss or an alarm condition) or up to 0.240 A of constant power on the
The Wheelock Power Supplies can accommodate 7 or 12 AH batteries inside its lockable chassis. Using an external battery cabinet it can charge up to 33 AH batteries (pending UL testing). Two FACP NAC circuits or two “Dry” contact initiating circuits can be connected to the inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs. Each output is rated at 3.0 Amps (Class “B”) or (Class “A”) and can be programmed to generate a steady or Code 3 Temporal Horn sound and a strobe output under alarm condition. Total load for the
The Power Suppliesunder
The
Approvals
•Approvals Include: UL Standard 864, 1481, California State
Fire Marshal (CSFM), Factory Mutual (FM)
•Compliant with NFPA 72
Inputs
•120VAC, 50/60Hz, 4.25 Amps
•240VAC, 60Hz, 2.42 Amps
Operating Power in Alarm
•24VDC Battery Backup Connection
•Two (2), 12V or 24V NAC Initiating Circuits
FWR or DC
•Two (2) “Dry” Contact initiating Circuits
•Accepts two (2) Class “A” or two (2) Class “B” circuit inputs
•Built in battery charger for sealed lead acid or gel type batteries
Outputs
•NAC outputs are 24VDC, 3.0 Amps each, power limited
•8 Amps on
U® L