•Capable of four (4), Class “B” circuits
•Capable of two (2) Class “A” circuits
•Capable of one (1) Class “A” circuit and two (2) Class “B” circuits
•Capable of (8) Class “B” or four (4) Class “A” circuits with optional
•Temporal (Code 3), constant voltage output, Wheelock Sync output or True input to output follower mode
•
•Input and output can be synchronized with “IN>OUT SYNC” mode (DSM, 2nd POWERPATH™ or FACP with synchronization protocol is required)
•Audible silence capability
•Filtered and electronically regulated output
•2.5 Amp auxiliary power limited output with reset capability. (Removed upon AC loss or alarm. Automatic reset 30 seconds after
AC power returns or the alarm condition is over) or 0.075 Amps
Supervision
•Compatible with 12V or 24V (FWR or DC) FACP
•Signaling appliance circuits are supervised and steered to either IN1 or IN2
•10K Ohm, 1 Watt (Wheelock Model #MPEOL) End of Line Resistor (EOLR) for supervision of all outputs
•37 distinguishable trouble diagnostics
•AC loss trouble reported over a separate set of contacts (delay of 1 second)
•All troubles are reported over the common trouble contacts (AC loss can have a delay of 30 seconds or 170 minutes)
•Automatic switchover to standby battery when AC fails
•Thermal and short circuit protection with auto reset
•Input and output status LED indicators
•AC fail supervision
•Battery presence and low battery supervision
•Ground Fault Detection, with diagnostics to indicate which circuit fault is on
•Latching LED’s for NAC trouble annunciation and Diagnostic trouble LED’s (latching can be disabled)
Power
•Not Battery Dependent
•Automatic switch over to standby batteries when AC fails
•Supports sealed lead acid or gel type batteries
•Fused battery protection
•Thermal and short circuit protection with auto reset
•Supports both 7AH or 12AH batteries in the same cabinet