PHOTOMETRICS

PHOTOMETRICS

IA, IC

 

 

IA-296T8 Energy Saving Ballast

IA-296T8 Energy Saving Ballast

F96T8/SPX35 Lamps 5950 Lumens

Spacing criterion:

(II)1.3 x mounting height, (F96T8/SPX35 Lamps 5950 Lumens) 1.5 x mounting height

Efficiency 89.4%

Test Report:

IA296T8.IES

LER = FI-84

Yearly Cost of 1000 lumens, 3000 hrs at

.08 KWH = $2.86

ORDERING INFORMATION

C o e ffi c i e n t s of Utilization

 

Effective floor cavity reflectance

 

20%

 

 

 

 

 

 

 

 

rc

 

80%

 

 

70%

 

 

50%

 

 

30%

 

 

10%

 

0%

rw

70

50

30

10

70

50

30

10

50

30

10

50

30

10

50

30

10

0

RCR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

105

105

105

105

102

102

102

102

96

96

96

90

90

90

86

86

86

83

1

95

90

86

83

92

88

84

81

83

80

77

78

76

73

74

72

70

68

2

85

78

71

65

82

75

69

64

71

66

62

67

63

59

64

60

57

55

3

77

67

59

53

74

65

58

52

62

56

51

58

53

49

55

51

47

45

4

70

59

50

44

68

57

49

43

54

47

42

51

46

41

49

44

40

37

5

64

52

44

37

62

51

43

37

48

41

36

46

40

35

43

38

34

32

6

59

46

38

32

57

45

37

32

43

36

31

41

35

30

39

34

29

27

7

54

42

34

28

52

41

33

28

39

32

27

37

31

26

35

30

26

24

8

51

38

30

25

49

37

30

24

35

29

24

34

28

23

32

27

23

21

9

47

35

27

22

45

34

27

22

32

26

21

31

25

21

30

24

20

19

10

44

32

25

20

43

31

24

20

30

24

19

29

23

19

27

22

18

17

Zonal Lumen Summary

Zone

Lumens

%Lamp

%Fixture

0-30

2152

18.1

20.2

0-40

3653

30.7

34.3

0-60

7182

60.3

67.5

0-90

9903

83.2

93.1

90-180

735

6.2

6.9

0-180

10637

89.4

100.0

C a n d e la

Angle

Along II

45o

Across

 

 

 

 

0

2668

2668

2668

 

 

 

 

10

2647

2619

2675

 

 

 

 

20

2521

2549

2640

 

 

 

 

30

2325

2441

2640

 

 

 

 

40

2052

2315

2619

 

 

 

 

50

1716

2171

2535

 

 

 

 

60

1303

1936

2199

 

 

 

 

70

847

1429

1359

 

 

 

 

80

336

473

259

 

 

 

 

90

8

29

22

 

 

 

 

100

3

160

174

 

 

 

 

110

3

296

336

 

 

 

 

120

5

220

438

 

 

 

 

130

6

113

284

 

 

 

 

140

8

26

139

 

 

 

 

150

9

11

27

 

 

 

 

160

8

8

11

 

 

 

 

170

8

6

8

 

 

 

 

180

7

7

7

 

 

 

 

Sample Number: IA-296T8-120V-EB81-U

Tandem

Blank = 4' Length 8T = 8' Length

Series

IA =Apertured Reflector IC =Closed Top Reflector

ICW =Extra Wide Channel

Reference STW Series with Symmetric Reflector

SilverLining 1

SS=Silver-Lining Housing and Ballast Cover

Number of Lamps

2 Lamps (Not Included)

Wattage

48 =40W T12 SL (48")

96 =75W T12 SL (72")

96T8 =59W T8 SL (96")

Voltage 2

120V =120 Volt

277V =277 Volt

347V =347 Volt

UNV =Universal Voltage 3

120-277

Options

GL=Single Element Fuse

GM=Double Element Fuse

Emergency =EM Installed

Ballast Type 2

LE3 =T12 Magnetic Energy

Saving

EB=Electronic Instant Start

ER=T8 Electronic Program

Rapid Start. Total

Harmonic Distortion < 10%

Lamp Size

2=T12

8=T8

Number of

Ballasts

1=1 Ballast

2=2 Ballast

Options

/PLUS=Higher Ballast Factor > 1.13.

Total Harmonic Distortion < 20%

RIF1 =Radio Interference Suppressor

6-3/18 SJT-C&P-L515P=Cord & Plug

(120V)

6-3/18 SJT-C&P-L715P =Cord & Plug

(277V)

TILW =Tandem In Line Wiring Option

(Consult TILW Option Catalog

Page)

POX =Porlux Finish

PI/CPI =Plug-In Option

Packaging

U=Unit Pack

4B =4 Bulk Packing

SHIPPING INFORMATION

Notes: 1 Silver lining not available on fixtures with HO.

2Products also available in non-US voltage and frequencies for international markets

3Not available when specifying emergencies, voltage must be specific

Catalog No.

Wt.

 

IA-248

16 lbs.

 

IA-296T8

30 lbs.

 

 

 

 

ACCESSORIES (Order Separately)

A1B/Spacer-U=Spacer 1-1/2" to 2-1/2" from ceiling (Use 2 per fixture)

GRP-SS=Gripper Hanger (Use 2 per fixture) SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48" Stem Set

AYC-Chain/Set-U=Chain Hanger Set (Use 1 set per fixture) WG/IC-4FT-U2=Wire Guard

CLC=Special Connector

(Additional Accessories Available. See Options and Accessories Section).

Specifications and Dimensions subject to change without notice.

ADF020759

Metalux • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801

09/17/2008 4:57:26 PM

Page 2
Image 2
Cooper Lighting 8520 IA-296T8 Energy Saving Ballast, F96T8/SPX35 Lamps 5950 Lumens Spacing criterion, LER = FI-84