Securing the fixtures with safety wire

Semi-recessed fixtures shown without thermal protectors

Installation Instructions

Sheet 3 of 5

 

 

 

Vault w/ visor

C-Scroll w/ visor

Roundel w/ visor

These installation instructions are valid with the above Ametrix styles.

Large, INDOOR

SRR

(Semi-Recessed, Remote ballast)

Visor and Non-Visor

Warning: Before starting any work ensure that all sources of power are turned off. All work must meet local/national codes and be performed by a certified electrician. Do not mount fixtures vertically.

4.

Securing the fixtures with safety wire

(both ceiling grid and drywall)

Safety wire (by others)

Fixture housing

1.After securing fixture housing to ceiling structure using provided brackets, reinforce fixture using safety wire(by others).

2.Using all four tabs located on corners of fixture housing, tie off fixture to structure using safety wire(by others).

5.

 

 

 

 

Wiring the fixture

Conduit

 

(both ceiling grid and drywall)

 

Electrical

(by others)

 

 

 

 

 

 

cover plate

 

 

 

 

 

 

Conduit nut

 

Conduit fitting

(by others)

Thermal cover

(by others)

 

 

plate

 

 

1.If applicable, replace ceiling tile with fixture secured back into ceiling. Remove adjacent tile from ceiling to facilitate wiring.

2.Loosen #10-32 x3/8" Pan head screws and remove electrical cover plate and knock out appropriate hole.

3.Using conduit fitting and nut, secure conduit to cover plate.

4.Attach appropriate wires and ensure all connections are properly matched. If ordered, remove thermal cover plate and wire thermal protector.

5.Replace cover plates and secure with #10-32 x3/8" Pan head screws.

ADY071461 REV A(ECN070344)