TROUBLESHOOTING

TROUBLESHOOTING

Trouble

 

Probable Cause

 

Remedy

UNIT WILL NOT RUN

A.

On–off switch in ”off” position.

A.

Turn switch to ”on”.

 

B.

Defective on–off switch.

B.

Check and replace.

 

C.

Blown fuse.

C.

Replace fuse and check for cause

 

 

 

 

of blown fuse.

 

D.

Thermostat set too warm for

D.

Adjust colder.

 

 

ambient.

 

 

 

E.

Power relay contacts

E.

Check and clean.

 

 

corroded.

 

 

 

F.

Defective thermostat.

F.

Check and replace.

 

G.

Loose electrical connection.

G.

Check wiring.

 

H.

Gearmotor overload protector

H.

Turn switch to off then to on.

 

 

has cut off machine.

 

 

 

 

 

 

 

COMPRESSOR CYCLES

A.

Low voltage.

A.

Check line voltage.

INTERMITTENTLY.

 

 

 

 

 

B.

Dirty condenser.

B.

Clean condenser.

 

C.

Air circulation restricted.

C.

Remove restriction.

 

D.

Defective condenser fan

D.

Check and replace.

 

 

motor.

 

 

 

E.

Defective relay, overload

E.

Check and replace.

 

 

protector or starting capacitor.

 

 

 

F.

Loose electrical connection

F.

Check wiring.

 

 

 

 

 