Remote Condenser Guidelines

Remote Condenser Guidelines

Remote Condenser Installation

For proper operation of the Cornelius ice machine, the following installation guidelines must be followed. Failure to do so may result in loss of production capacity, premature part failure, and may void all warranties.

Remote condensers must be installed per local building codes. A two to four inch diameter roof penetration will be needed for refrigerant lines and electrical conduit. The penetration should be within two feet of where the condenser will be located. A roof jack must be installed at the penetration.

Installation Guidelines

Ambient operating temperatures: -20°F (-28.9°C) to 120°F (48.9°C)

Maximum refrigerant line length: 60 ft. (18.29 Meters) RC14

Maximum vertical rise:16 ft. (4.88 Meters)

Minimum condenser height: CCM Series ice machine remote condensers must not be installed more than 6 feet (1.3 meters) below the refrigerant line quick connects at the rear of the ice machine. No part of the refrigerant lines, between the ice machine and the remote condenser, should fall below this point. Condensers must have a vertical airflow.

Air Flow

Page 4

Page 9
Image 9
Cornelius CCM CCU Air Flow, Remote Condenser Guidelines, Remote Condenser Installation, Installation Guidelines, Page