START--UP
IT IS IMPORTANT THAT THE LIQUID LEVEL SIGHT GLASS READS ”FULL”. IN THE EVENT THAT THE RESERVOIR IS EMPTY, THE UNIT WILL REMAIN OFF UNTIL AN ADEQUATE LEVEL OF LIQUID IS AT- TAINED. MAKE SURE CHILLER POWER IS ”OFF” PRIOR TO FILLING RESERVOIR.
Push CONTROL POWER button IN. All alarm indicators should be extinguished and the Chiller system will cycle in order to maintain the established
Thermostat Control
up
down
7
0
_F
out
set
FIGURE 3. CH SERIES TEMPERATURE CONTROLLER
The following procedure should be followed to adjust the thermostat for any liquid cooling application:
1.Push the ”SET”button located to the right of the digital display. This will display the current
2.The
3.Once the desired
The parameter settings of the thermostat have been preset at the factory. The range of the thermostat is 40_F (5_C) to 100_F (38_C). If operation outside of this range is desired, please contact the REMCOR TECHNICAL SERVICE DEPARTMENT at
CHILLER MAINTENANCE
WARNING: Disconnect electrical power before performing any maintenance on the Chiller.
Condenser
On air cooled chillers, the CONDENSER FINS should be cleaned by blowing compressed air through the con- denser from the fan side. Dirt and debris accumulate on the condenser fins over time, and this build up can se- verely reduce the performance of the Chiller. Cleaning of the CONDENSER FINS should be done approximately every three months, depending upon the cleanliness of your application.
Fan Motor
On air cooled chillers the condenser FAN MOTOR should be lubricated every 6 months with a few drops of SAE 10 oil.
5 | 92266 |