TROUBLE SHOOTING
|
|
|
| Jet Spray (Cold) Training Manual | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PROBLEM (fault) |
| CAUSE (diagnosis) |
|
| ACTION (remedy) |
|
|
|
|
| ||
| 5. Unit runs OK but short- | A. Overload protector |
| A. See “Compressor starts | ||
| cycles on |
|
|
|
| but then |
|
|
|
|
|
| on overload protector” |
|
|
|
|
|
| above |
|
| B. Thermostat |
| B. Widen differential | ||
|
|
|
|
| ||
| 6. Unit operates long or | A. Refrigerant low |
| A. Fix leak and charge | ||
| continuously | B. Control contacts stuck |
| B. Clean contacts or | ||
|
|
| closed |
|
| replace control |
|
| C. Refrigerated or air con- |
| C. Correct problem | ||
|
|
| ditioned space has |
|
|
|
|
|
| excessive load or poor |
|
|
|
|
|
| insulation |
|
|
|
|
| D. System is inadequate to |
| D. Replace with larger | ||
|
|
| handle the load |
|
| system |
|
| E. | Evaporator coil iced |
| E. | Defrost |
|
| F. | Restriction in refrigera- |
| F. | Determine location and |
|
|
| tion system |
|
| remove |
|
| G. Dirty condenser |
| G. Clean condenser | ||
|
| H. Filter dirty |
| H. Clean or replace filter | ||
|
|
|
|
| ||
| 7. Relay defective or | A. Incorrect relay |
| A. Replace with correct | ||
| burned out |
|
|
|
| relay |
|
| B. Incorrect mounting |
| B. Remount in correct | ||
|
|
| angle |
|
| position |
|
| C. Line voltage too high |
| C. Correct problem | ||
|
|
| or low |
|
|
|
|
| D. Excessive short cycling |
| D. Correct problem (see | ||
|
|
|
|
|
| “Unit runs OK but |
|
|
|
|
|
| |
|
| E. Relay mounting loose |
| E. Mount correctly | ||
|
| F. | Incorrect run capacitor |
| F. | Replace with correct |
|
|
|
|
|
| capacitor |
|
|
|
|
| ||
| 8. Suction line frosted or | A. Refrigerant overcharge |
| A. Correct charge | ||
| sweating |
|
|
|
|
|
|
|
|
|
| ||
| 9. Liquid line frosted or | A. Restriction in dehydra- |
| A. Replace bad part | ||
| sweating |
| tor or strainer |
|
|
|
|
|
|
|
|
|
|