INSULATED CHASE CONSTRUCTION

FIGURE 13: INSULATED CHASE

FACING

1.Combustible material must be installed flush with the fireplace. It may not project in front of or on the fireplace. This means that the steel front façade of the fireplace must not be overlapped with the combustible facing material. Figure 14 shows the proper installation of combustible material with reference to the fireplace front façade.

2.Non-combustible materials such as brick, stone or ceramic tile may project in front of and onto the steel front façade of the Inglenook Fireplace. Figure 15 shows the proper installation of non-combustible material with reference to overlapping the fireplace front façade.

MANTEL

The mantel must be installed at least 71 inches above the base of the fireplace. Figure 14 shows the proper location of the mantel with respect to the base of the fireplace.

Version: 7.0

24