Crestron DIN-AP2 DIN Rail Control Processor
Setup

Network Wiring

When wiring the Cresnet and Ethernet network, consider the following:
Use Crestron Certified Wire.
NOTE: Cresnet-HP wire cannot be used.
Use Crestron power supplies for Crestron equipment.
Provide sufficient power to the system.
CAUTION: Insufficient power can lead to unpredictable results
or damage to the equipment. Please use the Crestron Power
Calculator to help calculate how much power is needed for the
system (www.crestron.com/calculators).
Cresnet For networks with 20 or more devices, use a Cresnet Hub/Repeater
(DIN-HUB) to maintain signal quality.
For more details, refer to “Check Network Wiring” on page 29.
Ethernet The DIN-AP2 can also use high-speed Ethernet for communications with
other IP-based devices.
For information on connecting Ethernet devices in a Crestron system,
refer to the latest version of the Crestron e-Control® Reference Guide
(Doc. 6052), which is available for download from the Crestron website
(www.crestron.com/manuals).

Installation

The DIN-AP2 must be installed by a licensed electrician, in accordance
with all national and local codes.
CAUTION: This equipment is for indoor use only. Mount in a well
ventilated area. The ambient temperature must be 0º to 40º C
(32º to 104º F). The relative humidity must be 10% – 90%
(non-condensing).
Operations & Installation Guide – DOC. 6662A DIN Rail Control Processor: DIN-AP2 13