Hardware Hookup
Connect the
Device Make the necessary connections as called out in the illustration that
follows this paragraph. Refer to “Network Wiring” on page 8 before
attaching the 4-position terminal block connector. Apply power after all
connections have been made.
WARNING: Prior to connecting the device, turn off power at the circuit
breaker. Failure to do so may result in serious injury or damage to the
device. Restore power after all connections have been made.
NOTE: Install in accordance with all local and national electric codes.
NOTE: High-voltage connections accept 2.5 mm2 (12 AWG) wire. Wire
should be stripped to 8 mm (1/3 inch). Tighten terminal blocks to 0.5 Nm
(5 in-lbs).
NOTE: Use copper wire only. For high-voltage connections, use wire
rated for at least 75º C (167º F).
NOTE: Ensure the unit is properly grounded.
When making network connections to the DIN-PWS50, use a Crestron
power supply.
10 DIN Rail Power Supply: DIN-PWS50 Operations & Installation Guide – DOC. 6667A