All installations and services must be performed by qualified service personnel.

THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM BLOWER MOTOR. THE FOLLOWING SHOULD HELP ESTABLISH THE TYPE OF MALFUNCTION OR DEVIATION FROM THE NORMAL BLOWER OPERATION.

TO USE THIS DIAGRAM, YOU JUST NEED TO FOLLOW THE INSTRUCTIONS IN THE BOXES.

DOES BLOWER SPIN FREELY?

YES

IS THERE 115V

SUPPLIED TO MOTOR?

YES

DISCONNECT 16 PIN

HARNESS FROM MOTOR. IS THERE 12VDC ACROSS PIN12 & PIN1

AND PIN12 & PIN3

AT THE HARNESS PLUG?

 

 

CONFIRM IF EITHER BLOWER

 

NO

WHEEL IS RUBBING AGAINST

 

 

HOUSING OR MOTOR SHAFT

 

 

 

 

IS SPINNING FREELY, REPAIR

 

 

 

 

OR REPLACE AS NECESSARY.

 

 

 

 

CHECK 115V SUPPLY,

NO

CONNECTION FUSES,

 

SERVICE SWITCH AND

 

DOOR SWITCH.

 

 

 

 

 

 

 

 

IS THERE 24VAC

 

 

 

NO

ACROSS R &

NO

CHECK 24VAC

 

B/C ON THE

 

 

TO INTEGRATEDSUPPLY

CONTROL.

 

INTEGRATED

 

 

 

 

CONTROL?

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

YES

DISCONNECT 16PIN

HARNESS FROM

INTEGRATED CONTROL. IS THERE 12VDC ACROSS

PIN 6 & PIN 1

AT THE CONROL?

YES

CHECK HARNESS

CONNECTIONS

AND WIRE.

NOREPLACE INTEGRATED

CONTROL.

TURN THERMOSTAT MANUAL FAN

 

SWITCH ON (IF AVAILABLE) OR JUMPER

NO

BETWEEN R & G ON INTEGRATED CONTROL.

 

IS THERE VOLTAGE GREATER THAN

 

12VDC BETWEEN PIN15 & PIN1?

 

 

 

YES

 

CHECK CONNECTION ON HARNESS AND MOTOR,

RECONNECT HARNESS TO MOTOR, IF

CONNECTIONS ARE GOOD AND MOTOR STILL

DOES NOT RUN REPLACE MOTOR.

CHECK CONNECTIONS AND WIRES AT INTEGRATED CONTROL, IF OK REPLACE INTEGRATED CONTROL.

10

Page 12
Image 12
Crown CSHB60-90XE operation manual YES Is There Supplied to MOTOR? Disconnect 16 PIN