Crown Boiler BWC Series installation instructions Pipe and Circulator Sizing for Boiler Loop

Models: BWC Series

1 70
Download 70 pages 26.96 Kb
Page 27
Image 27

TABLE 8.5: PIPE AND CIRCULATOR SIZING FOR BOILER LOOP

 

(a)

(b)

(c)

(d)

BOILER MODEL

PIPE SIZE

FLOW

 

BOILER LOOP

CIRCULATOR

MAX EQUIVALENT

 

 

 

MODEL

LENGTH

 

(in NPT)

(GPM)

 

(ft)

 

 

 

 

 

BWC150

1 1/4

8.0

Taco 007

148

 

 

 

 

 

BWC150

1 1/4

8.0

Taco 0010

224

 

 

 

 

 

BWC225

1 1/4

12.0

Taco007

138

 

 

 

 

 

BWC225

1 1/4

12.0

Taco 0010

208

NOTE:

For piping method #1, “boiler loop” is heating system secondary loop

For piping method #2, “boiler loop” is heating system primary loop

TABLE 8.6: PIPE AND CIRCULATOR SIZING FOR INDIRECT WATER HEATER LOOP

 

(a)

(b)

(c)

(d)

(e)

(f)

BOILER

 

 

MAX. I.W.H.

 

 

I.W.H. LOOP MAX

PIPE SIZE

FLOW

PRESSURE

CROWN INDIRECT

CIRCULATOR

EQUIVALENT

MODEL

 

 

DROP

WATER HEATERS

MODEL

LENGTH

 

 

 

 

(in NPT)

(GPM)

(ft HEAD)

 

 

(ft)

 

 

 

 

MS-26, MS-40

 

 

BWC150

1 1/4

8.0

3.0

MSH-40H

Taco 007

26

 

 

 

 

MT040G, MT050G

 

 

 

 

 

 

MS-26, MS-40

 

 

BWC150

1 1/4

8.0

3.0

MSH-40H

Taco 0010

165

 

 

 

 

MT040G, MT050G

 

 

BWC150

1 1/4

8.0

5.0

MS-53, MS-79

Taco 0010

96

MSH053H (NOTE 1)

 

 

 

 

 

 

BWC150

1 1/4

10.0

5.0

MT079G (NOTE 1)

Taco 0010

38

 

 

 

 

 

 

 

 

 

 

 

MS-26, MS-40

 

 

BWC225

1 1/4

9.0

3.0

MSH-40H

Taco 007

90

 

 

 

 

MT040G, MT050G

 

 

BWC225

1 1/4

9.0

5.0

MS-53, MS-79

Taco 0010

97

MSH053H (NOTE 1)

 

 

 

 

 

 

BWC225

1 1/4

10.0

5.7

MT079G, MT100G

Taco 0010

60

(NOTE 2)

 

 

 

 

 

 

Note 1: MT100G or MS-119 can be installed with BWC150, Taco 0010 and up to 96ft of 1 1/4 piping, however catalog rating will not be achieved.

Note 2: MS-119 can be installed with BWC225, Taco 0010 and up to 60ft of 1 1/4 piping, however catalog rating will not be achieved.

25

Page 27
Image 27
Crown Boiler BWC Series installation instructions Pipe and Circulator Sizing for Boiler Loop